Manual background

2￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

Section 3-8

 

Select “Memory Switches”.

[ MAINTENANCE MENU ]

Quit

Display History

PT Setting Status

 

I/O Check

 

Memory Init.

 

Memory Switches

 

[ MEMORY SWITCH MENU (1/2) ]

Comm. Method

Host Link

EXIT

 

Key Press Sound

OFF

NEXT

Buzzer Sound

OFF

PAGE

Putting-Out Time

None

SAVE

Resume Function

ON

Support Tool Mode

NT600S

EXIT

 

Each time the “Putting-Out Time” touch switch is pressed, the setting option will switch among “10 min”, “1 hour”, and “None”.

Manual background Caution

Note

To set and quit the menu, press the [SAVE EXIT] touch switch. To quit without

￿setting, press [EXIT].

When “None” is set, the backlight OFF/EL screen OFF function is not effective and the same screen will therefore remain displayed indefinitely even if no op- eration is performed.

When “10 min” is set, the backlight or the EL screen will be turned off when no

￿operation has been performed for 10 minutes.

When “1 hour” is set, the backlight or the EL screen will be turned off when no operation has been performed for 1 hour.

Do not press touch switches carelessly while the backlight is off or while nothing is displayed on the screen.

Otherwise the system may operate unpredictably.

Only press touch switches after confirming system safety.

Continuous display of the same pattern for an extended time (as a guide, about 1 hour) will lead to the formation of an afterimage.

In order to prevent this, either periodically switch screens or use the EL screen OFF function.

￿￿

Page 111
Image 111
Omron V022-E3-1 operation manual Section, Select “Memory Switches”