Manual background

&￿￿￿-￿￿￿￿￿￿￿￿￿

 

Section 7-1

 

 

 

 

 

NT600S Symptoms

Cause

Remedy

 

 

 

 

 

Buzzer sounds, RUN LED

Malfunction due to external noise.

Distance the communication cable from the source of

 

is OFF.

 

the noise and insert a noise filter in the power supply

 

 

 

line.

 

 

 

 

 

Touch panel does not

Malfunction due to external noise

Distance the communication cable from the source of

 

respond

 

the noise and insert a noise filter in the power supply

 

 

 

line.

 

 

 

 

 

 

Touch panel is broken.

Check the touch panel by performing the touch panel

 

 

 

test in the I/O check in the maintenance mode.

 

PC mode changes to

The NT600S changes the mode

This is normal with the NT600S specification. When

 

monitor mode.

during host link communication.

using a PC that can also be connected using the NT

 

 

 

link, connect it with the NT link (the mode is not

 

 

 

changed when using the NT link).

 

￿￿￿

Page 256
Image 256
Omron V022-E3-1 operation manual Section