C500/C1000H rack-mounting type: C500-LK203

￿￿￿￿￿￿￿￿￿￿￿￿￿$￿￿￿￿￿&￿￿'￿￿(￿

Section 2-4

5V supply

ON

OFF

I/O port RS-422A RS-232C

Synchronization Internal External

Termination resistance

OFF

ON

CTS

0V External

C500/C1000H rack-mounting type: C500-LK203

[Setting the rear switches]

I/O port selection (selector switch)

￿Set this to “RS-232C”.

Unit #, parity, and transfer code (DIP SW1-1 to SW1-7) Set SW1-1 to SW1-7 to “OFF” (“0”).

Synchronization (selector switch)

￿Set this to “Internal”.

Baud rate (DIP SW2-1 to SW2-4)

Set these switches to “1010” to select 9600 bps. Set these switches to “0010” to select 19200 bps.

1-to-1/1-to-N selection (DIP SW2-6)

￿Set SW2-6 to “0” (1-to-N).

Instruction level (DIP SW2-7, SW2-8) Set these switches to “1”.

￿(Levels 1, 2, and 3 are enabled.)

CTS selection (selector switch) Set this always to “0V” (ON).

￿￿