Omron V022-E3-1 operation manual $& Section, Making the PC system settings, Switchsettings CPM1

Models: V022-E3-1

1 318
Download 318 pages 5.12 Kb
Page 55
Image 55
[Making the PC system settings]

￿￿￿￿￿￿￿￿￿￿￿￿￿$￿￿￿￿￿&￿￿￿'￿￿( Section 2-4

[Making the PC system settings]

The possible settings and existing settings which can be set by the PC system set- ting are as given below.

Item

Possible Setting

Existing Setting

 

 

 

Baud rate

2400/4800/9600/19200 bps

9600 bps

 

 

 

Stop bit

1 or 2 stop bits

2 stop bits

 

 

 

Parity

Even/odd/non-parity

Even parity

 

 

 

Data length

ASCII 7 bits

ASCII 7 bits

 

 

 

￿Unit #

00 to 31

Unit #00

C-series C200HS, C200HX/HG/HE, CPM1, CQM1

Set the operating conditions to the PC system setting area when a C200HS or CQM1 CPU is connected to the NT600S. The PC system setting area (data memory) can be directly accessed from the peripheral tool (LSS etc.).

The following describes the switch settings so as to enable the PC system set- tings. For the details of the operation with the PC system setting area, refer to the “SYSMAC CQM1 Reference Manual” (W228-E1- ￿).

[Switch settings] (C200HS,￿C200HX/HG/HE, CQM1)

CPU unit DIP switch settings

RS-232C port communication condition settings

Set DIP switch 5 to OFF (right side) to enable the PC system settings.

[Switch￿settings] (CPM1)

CPM1

-CIF01CPM1

Set the mode setting switch to the “HOST” (upper) position.

[PC system setting area settings]

Write settings to the PC system setting area (data memory) according to the port used to connect to the NT600S.

Channel #

Writing Value

Settings

 

 

 

DM6645

0001

Host link mode and conditions are set.

 

 

 

 

0303

Data length: 7 bits, 2 stop bits, even parity,

 

baud rate: 9600 bps

DM6646

 

 

 

0304

Data length: 7 bits, 2 stop bits, even parity,

 

 

baud rate: 19200 bps

 

 

 

 

 

DM6648

0000

Unit No. 0

￿￿

Page 55
Image 55
Omron V022-E3-1 $& Section, Making the PC system settings, Switch settings C200HS,C200HX/HG/HE, CQM1, Switchsettings CPM1