Omron V022-E3-1 Touch Switch Number Output from NT600S to Host, PT Battery Status Response

Models: V022-E3-1

1 318
Download 318 pages 5.12 Kb
Page 235
Image 235
Touch Switch Number Output (from NT600S to Host)

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

Section 6-3

Touch Switch Number Output (from NT600S to Host)

Format

[ESC] H m1 m2 m3 [CR]

1B

48

0D

 

m1m2 m3: Address of the pressed touch switch (3-digit hexadecimal)

 

000 to 0E2H, 0E7 to 0FEH (0 to 226, 231 to 254)

Description

If a touch switch is pressed while the screen for which the “Bit In = Off” attribute is

 

set is displayed, the address of the pressed touch switch is reported to the Host.

Reference If more than one touch switch is pressed at the same time, only the address of the touch switch which was pressed first is reported to the Host.

When a touch switch which is set as a ten key switch (231 to 254) is pressed, it is

￿not reported to the Host.

When a touch switch which is set as a system key (227 to 230, 255) is pressed, it is not reported to the Host.

Notifying Low Battery Voltage

The status of the battery in the NT600S is sent to the Host by executing the follow- ing command.

PT Battery Status Response

Format

[ESC] [ m1 m2 [CR]

1B

5B

0D

 

m1m2: Battery voltage status (2-digit hexadecimal)

 

00

(30H 30H): Normal voltage

 

01

(30H 31H): Low voltage

Description

The NT600S returns this command to report the battery voltage status to the Host

 

in response to the PT Battery Status Enquiry Command (refer 7-2-4 PT Battery

 

Status Enquiry) sent from the Host.

Whether or not report is made is determined by the ON/OFF setting of DIW

SW2-8.

￿￿￿