Omron V022-E3-1 operation manual Appendix D, NT600S Installation Environment

Models: V022-E3-1

1 318
Download 318 pages 5.12 Kb
Page 277
Image 277
Appendix D

￿￿￿￿￿￿%￿￿￿￿￿￿￿￿￿￿￿6￿9￿￿￿￿￿￿￿￿

Appendix D

APPENDIX D

NT600S Installation Environment

When installing the PT in the operation panel, observe the following points. See also the section “Getting Starting”.

The view angle of the LCD screen is 50￿to the left and 40￿to the right. Install it at a position and height where

￿operators will be able to see it well.

Do not install the unit at locations where the ambient temperature goes outside the range 0 to 50￿C or where the relative humidity goes outside the range 35 to 85% RH.

If the ambient temperature exceeds the range indicated above, install a fan or an air conditioner.

Louvre

Fan

PT

Control panel

Provide sufficient space for ventilation

Do not install the unit directly above equipment that generates a lot of heat (heaters, transformers, large capacity resistors, etc.)

To ensure that the unit can be operated and maintained without difficulty, install it at a distance from high-voltage

￿equipment and power equipment.

Install the unit as far as possible from personal computers, amateur radio equipment, radios, etc. The radio waves generated by the unit may￿cause interference that will affect these types of equipment.

APPENDIX D Caution Do not install the NT600S at sites subject to the following conditions.

Otherwise, the product may malfunction.

Severe temperature variations

Temperatures or humidities outside the ranges stated in the specifications

High humidity, condensation

Splashing chemical agents

Severe oil splashing

Corrosive or flammable gases

Strong vibrations or shocks

Direct exposure to wind and rain (outdoor sites)

￿Strong ultra-violet irradiation

Take adequate measures to ensure shielding if the NT600S is used at a location subject to any of the following conditions.

Otherwise, the product may malfunction.

Static electricity, or noise from other equipment

Strong electromagnetic fields

Nearby power cables

Potential exposure to radioactivity

￿￿￿

Page 277
Image 277
Omron V022-E3-1 operation manual Appendix D, NT600S Installation Environment