Cautions on replacing the NT600S

%￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿

Section 7-4

Points inspected

Inspect the following points to determine if there is any divergence from the stated criteria. If there is, either improve the surrounding environment so that the values fall within the stated range, or adjust the NT600S.

Point Inspected

Inspection Details

Criterion

Inspection Instrument

 

 

 

 

Power supply voltage

Fluctuation in power supply

Permissible voltage fluctuation

Tester

 

terminal voltage

range

 

 

 

(24 VDC --15% +10%)

 

 

 

 

 

Ambient environmental

Ambient temperature

0 to 50￿C

Thermometer

conditions

(temperature in the operation

 

 

 

panel)

 

 

 

 

 

 

 

Ambient humidity

35% to 85%RH

Hygrometer

 

(humidity in the operation

 

 

 

panel)

 

 

 

 

 

 

 

Presence/absence of dust

Dust must not be settled

Visual inspection

 

 

 

 

Mounting conditions

Looseness of mounting

To be no looseness

Accessory tools

 

brackets etc.

 

 

 

Connector connections of

To be fully inserted and locked,

 

 

connecting cable

with no looseness

 

 

Looseness of screws in

To be no looseness

Philips screwdriver

 

external wiring

 

 

 

Conditions of external

Faults such as incipient

Visual inspection

 

connecting cables

disconnections.

 

Components with limited

Brightness of the backlight

Must be sufficiently bright.

Visual inspection

lives

 

Backlight life:

 

 

 

 

 

 

Brightness is halved after

 

 

 

about 20,000 hours in use.

 

 

 

 

 

 

Brightness of EL display unit

Must be sufficiently bright.

Visual inspection

 

 

EL display unit life:

 

 

 

Brightness is reduced by 30%

 

 

 

after about 30,000 hours in

 

 

 

use.

 

Manual background Caution Do not disassemble for repairs or modification. Otherwise, the product may

￿malfunction.

The disposal of the NT600S (and used backlights) may be regulated by national or local authorities. Dispose of them in accordance with the laws and regula- tions of the relevant country and local authority.

Cautions on replacing the NT600S

When replacing the NT600S after discovering a fault during inspections, note the following points:

Be sure to switch the power OFF before replacement.

￿After replacement, check that the new NT600S is not subject to the same error.

If a faulty unit is returned for repairs, write as detailed a description of the fault as possible and send this description together with the unit to the OMRON address indicated on the back cover of this book.

￿￿￿