3-5-3 PC Switch Settings

￿￿￿￿￿￿￿￿￿￿￿￿￿$￿￿￿￿￿￿￿'￿￿()*+*,

Section 2-5

3-5-3 PC Switch Settings

When the NT600S and PC are connected to each other, set the conditions at the

PC CPU so as to enable the NT link communications.

￿The following is a general description of switch settings.

C-series C200HS, C200HX/HG/HE, CPM1, CQM1

Set the operating conditions to the PC system setting area when a C200HS or CQM1 CPU is connected to the NT600S. The PC system setting area (data memory) can be directly accessed from the peripheral tool (LSS etc.).

The following describes the switch settings so as to enable the PC system set- tings. For the details of the operation with the PC system setting area, refer to the “SYSMAC CQM1 Reference Manual” (W228-E1- ￿).

[Switch setting] (C200HS,￿C200HX/HG/HE, CQM1)

CPU unit DIP switch settings

RS-232C port communication condition settings

Set DIP switch 5 to OFF (right side) to enable the PC system settings.

[PC system setting area settings] (C200HX/HG/HE, CPM1, CQM1)

Write values to the PC system setting area (data memory) in accordance with the

CPU unit and port used for connection to the NT600S.

PC Side

Channel #

Writing Value

Settings

 

 

 

 

RS-232 port of

 

 

 

C200HX/HG/HE,

DM6645

 

 

CQM1

 

 

 

 

 

 

 

Port A of C200HX/

DM6555

4000

Use NT link (1:1)

HG/HE

 

Port B of C200HX/

DM6550

 

 

HG/HE

 

 

 

 

 

CPM1

DM6650

 

 

 

 

 

 

￿￿

Page 59
Image 59
Omron V022-E3-1 operation manual 3-5-3PC Switch Settings, Section, Switch setting C200HS,C200HX/HG/HE, CQM1