Manual background

￿.￿￿￿￿￿￿￿￿.￿(￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿$￿0&￿￿￿

Appendix E

Wiring Connections

CVM1/CV-series host link units have two types of connector, which must be wired differently.

The NT600S does not use pin 4 (RS) or pin 5 (CS). Either short the RS and CS pins of the PC connector together or set the CTS setting selector switch at the rear face of the host link unit to “0V” (see ￿in the figure).

Connect the cable shielding wire to the connector cover and pin 1 at the host link unit end of the cable only.

Communication Port 1 (25-pin Connector)

NT600S

 

 

￿

PC (host link unit)

 

 

Abbrevi-

Pin

Pin

Abbrevi-

 

 

atioon

number

number

atioon

 

 

FG

1

1

FG

 

 

SD

2

2

SD

 

 

RD

3

3

RD

RS-232C

RS-232C

RS

4

4

RS

interface

interface

CS

5

5

CS

 

 

 

 

+5V

6

6

--

 

 

--

7

 

7

SG

 

 

--

8

Shielding

8

--

 

 

SG

9

--

--

 

 

wire

 

 

 

 

--

--

 

 

 

 

 

 

 

 

 

 

--

--

 

 

 

 

 

--

--

 

 

 

 

 

20

ER

 

 

 

 

 

25-pin connector

 

Communication Port 2 (9-pin Connector)

NT600S

 

Abbrevi-

Pin

 

atioon

number

 

 

 

 

FG

1

 

SD

2

 

RD

3

RS-232C

RS

4

interface

CS

5

 

 

+5V

6

 

--

7

 

--

8

 

SG

9

PC (host link unit)

PinAbbrevi-

number atioon

￿Connector cover FG

2SD

3RD

4

RS

RS-232C

interface

5CS

6--

7CD

-- --

9SG

9-pin connector

Shielding wire

￿￿￿

Page 284
Image 284
Omron V022-E3-1 Appendix E, Wiring Connections, Communication Port 1 25-pinConnector, Communication Port 2 9-pinConnector