2-4-1 What is the NT Link (1:N)

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

Section 1-4

2-4-1 What is the NT Link (1:N)

The NT link uses the direct connection function and can execute high-speed com- munications with the CPU units (with built-in host link) of the CPM1, CQM1, C200HS, C200HX/HG/HE, or CVM1/CV series.

When using the NT600S in an NT link, two communications modes are possible: a single NT600S can be connected to one PC (1:1 NT link), or alternatively, up to eight NT600S units can be connected to a single PC port (1:N NT link).

However, the 1:N connection NT link can be used with C200HX/HG/HE only. In the following sections, the NT link communication mode in general will be indicated by the term “NT link”, a 1:1 connection NT link will be indicated by

“NT link (1:1)”, and a 1:N connection NT link will be indicated by “NT link (1:N)”.

Features of the NT Link

The NT link method has the following features.

￿It allows high-speed communications with a specific PC.

Data can be written to the memory area of the PC in bit units.

This means that different bits of the same word to which a touch switch is allo- cated can be used for different applications (for example the allocation of a lamp).

However, since data is written to the DM area in word units, it is not possible to use the other bits of words to which touch switches have been allocated for other applications in the case of this area.

Can be used even while the PC is in the run mode. When using a host link, the

NT600S switches from the run mode to the monitor mode.

With NT link (1:N), up to eight NT600S units can be connected to a single PC port ￿and used simultaneously.

When using C200HX/HG/HE, by installing an expansion communication board in the option slot of the CPU unit, it is possible to connect up to three NT link (1:N) systems (comprising a total of 24 NT600S units). For details on communication boards, refer to the “SYSMAC C200HW-COM01 to C200HW-COM06-E Com- munication Board OPERATION MANUAL” (W304-E1-￿).

 

Since there is compatibility between the NT link and host link, the host link direct

 

connection data can be used without alteration for the NT600S screen data and

 

PC programs.

Reference

 

When communication is conducted in a 1:N NT link, RS-232C/RS-422 converter

 

units (NT-AL001) must be used for the connections to the individual PTs.

Note

 

 

When an NT600S-ST121(B)-EV ￿is connected, a +5 V (150 mA) power supply is

 

required for the converter. Do not draw the power supply from the PT.

 

 

￿￿