Omron V022-E3-1 operation manual 3-2-3Grounding, Section

Models: V022-E3-1

1 318
Download 318 pages 5.12 Kb
Page 43
Image 43
3-2-3 Grounding

%￿￿￿￿￿￿￿￿￿￿￿

Section 2-2

Manual background Caution Fit crimp-style terminals to the power cable. Connecting the wires of the cable to the terminal block directly after merely twisting them together could cause fire and other hazards.

Fork type

Round type

7 mm or less

7 mm or less

[Recommended terminals]

Maker

Type

Type

Applicable Wire

(fork type)

(round type)

(stranded wire)

 

 

 

 

 

Japan Solderless Terminal MFG

2-YS3A

2-3.5

 

 

 

 

1.04 to 2.63 mm2

Fuji Terminal

2-YAS3.5

V2-S3.5

Nichifu Terminal

2Y-3.5

2-3.5

 

3-2-3 Grounding

The NT600S has a Grounding terminal Manual background .

Note To prevent malfunctions due to excessive noise, and to prevent electric shock, carry out class 3 grounding (grounding resistance of 100 ￿or less) using a spe- cial-purpose grounding cable (wire of at least 2 mm2).

Grounding wire length should be less than 20 m.

Note that if grounding wire is used in common with other equipment, or if it is con- nected to a beam of a building, for example, the NT600S might be adversely af- fected by this grounding.

Other

NT600S equipment

Class 3 grounding (grounding resistance is 100 Ω or less)

Grounding for individual equipment: Correct

NT600S

Other

NT600S

Other

equipment

equipment

 

 

Grounding common to several pieces of equipment: Incorrect

Manual background Caution Carry out class 3 grounding (grounding wire must be less than 100￿) before con- necting the power supply. Otherwise there will be a danger of electric shock.

￿￿