Connecting to a Host Link Unit

￿￿￿￿￿￿￿￿￿￿￿￿￿$￿￿￿￿￿&￿￿￿'￿￿(

Section 2-4

Connecting to a Host Link Unit

Two types of host link units are available: a rack-mounting type and a CPU- mounted type. The switch settings differ according to the type of host link unit. Set ￿the switches according to the unit type.

C200H rack-mounting type: C200H-LK201(-V1)

[Setting the front switches]

Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree￿with the following.

 

 

 

Unit # (SW1, SW2)

 

 

￿

Set these switches to “0”.

 

 

 

Instruction level, parity, and transfer code (SW4)

5

2

￿

Set this switch to “2”.

Baud rate (SW3)

Set this switch to “5” to select 9600 bps.

Set this switch to “6” to select 19200 bps.

[Setting the rear switches]￿

1-to-1/1-to-N selection (DIP switch) ￿Set #3 to “ON”.

CTS selector switch

ExternalCTS selection (selector switch)

Set this always to “0V” (ON).

0V￿(ON)

C500/C1000H rack-mounting type: C500-LK201-V1

[Setting the front switches]

Host

Local

￿Mode control (key switch) Set this to “host link”.

￿￿