Omron V022-E3-1 Communications Specifications, Appendix A, For a Host Link, For an NT Link 1:1

Models: V022-E3-1

1 318
Download 318 pages 5.12 Kb
Page 272
Image 272
Communications Specifications

￿￿￿￿￿￿￿￿￿￿￿￿￿￿

 

 

 

Appendix A

Communications Specifications

 

 

[For a Host Link]

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

Specification

 

 

 

 

Communications standard

 

 

EIA RS-232C

 

 

 

 

Communications settings

 

 

Start-stop synchronization

 

 

 

Baud rate: 9600, 19,200 bps

 

 

 

Data length: 7 bits

 

 

 

Stop bit:

2 bits

 

 

 

Parity:

Even

 

 

 

 

Connector

 

 

9-pin, D-SUB connector (female)

 

 

 

 

 

 

Number of units connected

 

 

1 to 1

 

 

 

 

 

 

 

 

Transmission distance

 

 

Max. 15 m

 

 

 

 

 

 

Communications protocol

 

 

C-series SYSWAY (1:N)

 

 

 

 

 

 

[For an NT Link (1:1)]

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

Specification

 

 

 

 

Communications standard

EIA RS-232C

 

 

 

 

Connector

9-pin D-SUB connector (female)

 

 

 

 

 

Number of units connected

1 to 1

 

 

 

 

 

 

 

 

Transmission distance

Max. 15 m

 

 

 

 

 

 

 

 

 

[For an NT Link (1:N)]

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

Specification

 

 

 

 

Communications standard

EIA RS-232C

 

 

 

 

Connector

9-pin D-SUB connector (female)

 

 

 

 

 

Number of units connected

1:1 to 8

 

 

 

 

 

 

Transmission distance

￿RS-232C cable

: Max. 2 m (*)

 

RS-422A/485 cable

: Total length 500 m (*)

 

 

 

 

(*)When NT-AL001 used

[For RS-232C]

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

Specification

 

 

 

 

Communication standard

EIA RS-232C

 

 

 

 

Communication settings

Start-stop synchronization

 

Baud rate:

2400/4800/9600/19200 (bps)

 

Data length: 7, 8

 

 

 

Stop bit:

1, 2

 

 

 

Parity:

Even/Odd/None

 

Flow control:RS/CS control

 

 

 

XON/XOFF control

 

 

 

None

 

 

 

 

 

 

Connector

9-pin D-SUB (female)

 

 

 

 

 

 

 

Number of units connected

1-to-1

 

 

 

 

 

 

 

 

Transmission distance

Max. 15 m

 

 

 

 

 

 

 

 

 

￿￿￿

Page 272
Image 272
Omron V022-E3-1 Communications Specifications, Appendix A, For a Host Link, For an NT Link 1:1, For an NT Link 1:N