| Maximum Power Consumption, | This represents total input power. | 
| Modular Configuration | 
 | 
| 
 | 
 | 
| Maximum DC | 9.5 kW (assuming 88% efficiency) | 
| 
 | 
 | 
| Maximum AC | 9.8 kW (assuming 92% efficiency) | 
| 
 | Note Proper grounding is also required at the site to | 
| 
 | ensure that equipment is not damaged by | 
| 
 | lightning or power surges. | 
| 
 | 
 | 
| DC Power Lug Torque Ranges | 
 | 
| 
 | 
 | 
| Minimum torque | 20  | 
| 
 | 
 | 
| Maximum torque | 30  | 
| 
 | 
 | 
| Power Redundancy, Fixed | 
 | 
| Configuration | 
 | 
| 
 | 
 | 
| DC | 2N: Three “A” battery plant feeds for one PDU, and | 
| 
 | three “B” battery plant feeds for the other PDU | 
| 
 | 
 | 
| AC (Delta or Wye  | 2N: Two independent Delta or Wye  | 
| 
 | sources required | 
| 
 | 
 | 
| Power Redundancy, Modular | 
 | 
| Configuration | 
 | 
| 
 | 
 | 
| DC | 2N: Up to four A battery plant feeds and up to four B | 
| 
 | battery plant feeds required. | 
| 
 | 
 | 
| AC | 2N: Up to three A AC  | 
| 
 | up to three B AC  | 
| 
 | 
 | 
| Inrush current, Fixed Configuration | 
 | 
| 
 | 
 | 
| DC | 75 A | 
| 
 | 
 | 
| AC | 160 A | 
| 
 | 
 | 
| Inrush current, Modular | 
 | 
| Configuration | 
 | 
| 
 | 
 | 
| DC | 90 Apk max | 
| 
 | 
 | 
| AC | 30 Apk max | 
| 
 | 
 | 
| DC Input, Fixed Configuration | 
 | 
| 
 | 
 | 
| Nominal input voltage | |
| 
 | |
| 
 | |
| 
 | (range  | 
| 
 | 
 | 
| Input current | 56 A (nominal) | 
| (PDU rated for 60 A) | 66 A at  | 
| 
 | 
 | 
| DC Input, Modular Configuration | 
 | 
| Nominal input voltage | |
| 
 | |
| 
 | (range  | 
| 
 | 
 | 