Appendix A Cisco CRS Carrier Routing System
Table
Maximum Power Consumption, | This represents total input power. |
Modular Configuration |
|
|
|
Maximum DC | 9.5 kW (assuming 88% efficiency) |
|
|
Maximum AC | 9.8 kW (assuming 92% efficiency) |
| Note Proper grounding is also required at the site to |
| ensure that equipment is not damaged by |
| lightning or power surges. |
|
|
DC Power Lug Torque Ranges |
|
|
|
Minimum torque | 20 |
|
|
Maximum torque | 30 |
|
|
Power Redundancy, Fixed |
|
Configuration |
|
|
|
DC | 2N: Three “A” battery plant feeds for one PDU, and |
| three “B” battery plant feeds for the other PDU |
|
|
AC (Delta or Wye | 2N: Two independent Delta or Wye |
| sources required |
|
|
Power Redundancy, Modular |
|
Configuration |
|
|
|
DC | 2N: Up to four A battery plant feeds and up to four B |
| battery plant feeds required. |
|
|
AC | 2N: Up to three A AC |
| up to three B AC |
|
|
Inrush current, Fixed Configuration |
|
|
|
DC | 75 A |
|
|
AC | 160 A |
|
|
Inrush current, Modular |
|
Configuration |
|
|
|
DC | 90 Apk max |
|
|
AC | 30 Apk max |
|
|
DC Input, Fixed Configuration |
|
|
|
Nominal input voltage | |
| |
| |
| (range |
|
|
Input current | 56 A (nominal) |
(PDU rated for 60 A) | 66 A at |
|
|
DC Input, Modular Configuration |
|
Nominal input voltage | |
| |
| (range |
|
|
Cisco CRS Carrier Routing System
|
|
| |
|
|