Bosch Appliances D9412GV2 manual Parity/Stop, DTR Control, Supervision, RTS Control, Status Rate

Models: D9412GV2

1 158
Download 158 pages 17.38 Kb
Page 127
Image 127
Parity/Stop

D9412GV2/D7412GV2 Program Entry Guide 6.0 GV2AUX

EN 127

Parity/Stop

Default:

No/1

Selection:

No/1, No/2, Odd/1, Even/1

No/1

No parity, 1 stop bit

 

 

No/2

No parity, 2 stop bits

 

 

Odd/1

Odd parity, 1 stop bit

 

 

Even/1

Even parity, 1 stop bit

 

 

This prompt addresses two items: parity and the number of stop bits. Pressing the [SPACE] bar on the D5200 toggles through the available options.

DTR Control

Default:

On

Selection:

On, AutoD, Off

On

Sets DTR to on (hardware control).

 

 

AutoD

Sets this to Auto DTR.

 

 

Off

Sets DTR off (hardware control).

 

 

This item determines how the Data Terminal Ready (DTR) Control parameters are defined for the D9133. Pressing the [SPACE] bar on the D5200 toggles through the available options.

9133 Supervision

Default:

No

Selection:

Yes or No

Yes

Supervise the serial interface

 

module (SIM).

 

 

No

Do not supervise the serial interface

 

module (SIM).

This item determines whether the serial interface module (SIM) is supervised or not. If the SIM is supervised, disconnecting the SIM from the control panel creates a Trouble SDI 80 Event and the keypad annunciates a trouble tone (if programmed) and displays SERVC SDI 80.

Trouble SDI 80 Reports are always sent using the account number for Area 1.

RTS Control

Default:

On

Selection:

On, AutoX, Off, AutoR

On

Sets RTS to on (hardware control).

 

 

AutoX

Automatically enables Xon/Xoff

 

(software control).

 

 

Off

Sets RTS off (hardware control).

 

 

AutoR

Sets this to Auto RTS.

 

 

This item determines how the Request To Send (RTS) Control parameters are defined for the serial interface module (SIM). Pressing the [SPACE] bar on the D5200 toggles through the available options.

Status Rate

Default:

0

Selection:

0 to 255

0

Status information is sent only when

 

requested.

 

 

1 to 255

Status information is sent at the

 

interval programmed.

If the Status Rate is set to a value less

than 10, and 1 to 6 SDI devices are

connected to the system, the fastest the control panel can send the status information is in approximately 1 sec. If more than six SDI devices are connected to the control panel, the fastest the control panel can send the information is in approximately 1.5 sec to 2 sec.

This item determines how often the default status information is sent to the serial interface module (SIM). The status information includes:

The current point status (normal or off-normal),

The control panel’s area status (Master Armed, Master Instant Armed, Perimeter Delay Armed, Perimeter Instant Armed, Disarmed, Area Entry Delay, Perimeter Entry Delay, Area Exit Delay, and Perimeter Exit Delay)

The control panel status (AC Fail, Battery Missing, AC Restore, Battery Low, and so on)

Relay status (relay on or relay off)

Entries are in 100 millisecond increments. If a 5 is entered, the status information is sent every 500 milliseconds (or 0.5 sec). An entry of 10 equals 1 sec.

Bosch Security Systems, Inc. 10/08 F01U003636-04