P## BP Retrnable

D9412GV2/D7412GV2 Program Entry Guide 4.0 RADXPNTS

EN 99

P## BP Retrnable

Default:

No

Selection:

Yes or No

Yes

This point automatically returns to

 

the system when the area is

 

disarmed.

 

 

No

This point stays out of the system

 

through arming and disarming

 

cycles.

 

 

Use this option to return a point that was bypassed, force armed, or swinger bypassed back into the system when the area to which this point is assigned is disarmed. This option applies to all point types.

Set this item to No for Interlock points.

When the point cannot return to the system through disarming, the point must be manually unbypassed using the Unbypass?, keypad function, Sked Functions 4 and 5, or remote programming software (RPS).

For Force Armed points to remain bypassed, ensure that P## FA Retrnable is set to No.

P## Bypassable

Default:

No

Selection:

Yes or No

Yes

This point can be bypassed and

 

force armed.

 

 

No

This point cannot be bypassed or

 

force armed from the keypad or

 

remote programming software

 

(RPS); however, it can be force

 

armed by automatic arming at the

 

end of the Closing Window (refer to

 

the A# Auto Close prompt in

 

Section 2.9.5 Open/Close Options

 

on page 43 or by a Sked

 

programmed to arm the area.

 

 

To meet UL 864 requirements, set this parameter to No.

Use this option to allow this point to be bypassed or force armed.

Bypassing a 24-hour point: When a 24-hour point or 24-hour Supervisory point is bypassed, 24 HOUR BYPASS scrolls continuously at the keypad.

Bypassing a Fire Point: FIRE BYPASS scrolls to indicate that a 24-hour Fire point or a Fire Supervisory point is bypassed.

Alternative to a 24-hour Point: For alarm capability of a 24-hour point without the continuous scrolling, use a Perimeter point with a Point Response of 9 to E.

If the P## Bypassable option is set to Yes, a point can be bypassed in several ways. Refer to Table 31.

Table 31: Bypassing a Point

 

 

Bypass with:

Report sent:

Keypad using the Bypass?

Command Bypass

function

 

Keypad using Command 0

Command Bypass

Sked Function 3

Sked Bypass

Remote programming software

RPS Bypass￿

(RPS)

 

￿RPS Bypass is sent at the end of the RPS session.

If the P## Swinger Byps option is set to Yes, a point is automatically bypassed after the fourth alarm or trouble report is sent. A swinger Bypass report is sent at the same time.

Programming Bypassable as Yes for Cross Points can cause missed Cross- Point alarms. For example, if Points 1 and 2 were programmed as Cross Points and Point 1 was Bypassed or Force Armed, Point 2 cannot generate an Alarm Cross Point Event. Point 2 can; however, generate an Unverified or Alarm Event depending on how the point was faulted. Be careful when using this feature with Cross Point applications.