Path # Poll Rate: 75 sec

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 25

UL 864 Enhanced Communication Path Report Prioritization:

To ensure that high priority events such as Fire Alarms are reported before any other queued event reports, use Route Groups 1 and 2. The lower numbered route groups are higher priority than the higher numbered route groups. For example, the following route groups are listed from highest priority to lowest priority: RG1￿RG2￿RG3￿RG4.

UL 864 Enhanced Communication Path Supervision:

To detect and locally annunciate a break in an Enhanced Communication Path in less than 200 sec, program no more than two Enhanced Communication Paths in no more than two Route Groups. Use the following settings for both Enhanced Communication Paths:

Path # Poll Rate: 75 sec

Path # ACK Wait: 13 sec

Path # Retry Count: 5

If the External Modem feature is used, RG# Primary SDI and RG# Backup SDI must be set to No. The control panel supports either enhanced communication or external modem, but not both at the same time.

RG# Primary SDI

The poll rate entry for the backup SDI path might need to increase because of heavy traffic on the network or excessive signals generated at the same time. All Comm prompts must be set to No.

RG# Primary Pager

Default: No

Selection: Yes or No

This parameter determines if this route group sends events to a numeric pager. To send events to a numeric pager, a phone number must also be programmed in the route group’s primary destination.

If programming the control panel to dial a numeric pager, choose its route group carefully. Place events being sent to a central station in a route group class with a lower number than the numbers of the events in the route group for the numeric pager.

2.4.3Numeric Pager Capability

The D9412GV2 and D7412GV2 Control Panels can send most events to a numeric pager. Any time an event is generated and routed to a numeric pager, the control panel calls the numeric pager once for each message in the queue. To enable the pager, program the primary phone number and the backup phone number to the numeric pager’s phone number in any of the four route groups. Then select which events to route to the numeric pager within the selected route group.

Default: No

Selection: Yes or No

This parameter determines if the primary destination for Route Group 1 (2, 3, or 4) is sent to the NIM

RG# Backup SDI

Up to four event fields can be shown in the pager message. Refer to Figure 1.

Default: No

Selection: Yes or No

This parameter determines if the backup destination for Route Group 1 (2, 3, or 4) is sent to the NIM.

To completely disable Enhanced

Routing over an SDI path, RG# Primary

SDI,

RG# Backup SDI, and Enhanced

Comm prompts must be set to No.

Bosch Security Systems, Inc. 10/08 F01U003636-04