D9412GV2/D7412GV2 Program Entry Guide 4.0 RADXPNTS

EN 101

The Cross Point feature does not activate when a fault occurs on Controlled points (Point Types 1, 2 and 3) in the disarmed, entry delay, or exit delay states. Refer to Section 6.9 Cross Point Parameters on page 142 for additional programming requirements to program the Cross Point Timer.

If an abort window delay is needed for the cross zone alarms, all cross zone points in the group must have P## Alarm Abort (refer to page 102)set to Yes.

The Cross Point function applies only to Instant Alarm conditions. It does not apply to Trouble or Supervisory conditions.

For SIA CP-01 Compliance:

P## Cross Point can be set to Yes or No.

P## Fire Point

Default: No

Selection: Yes or No

 

Yes

 

This point is a Fire point.

 

 

 

 

 

No

 

This point is not a Fire point.

 

 

 

 

 

 

 

 

 

To meet UL 864 requirements, set this

 

 

 

 

parameter to Yes for all applicable Fire

 

 

points.

 

 

 

 

Use this option to make a 24-hour point a Fire point. This option makes this point the highest priority event in the control panel when an alarm occurs for both reporting and displaying on the keypad. Refer to Section 4.2.2 Characteristics of a Fire Point on page 92.

You should dedicate a fire annunciation device to all your Fire points if they are assigned to a single area in a multiple area system. Special red keypads and annunciators with specific keys for fire systems are designed for this type of application (D1256RB and D1257RB).

Do not use the Cross point function for

Fire points.

P## Alarm Verify

Default:

Refer to the program record sheet

Selection:

Yes or No

Yes

Enable alarm verification on this

 

point.

 

Alarm verification points must be

 

programmed as resettable.

 

 

No

Disable alarm verification on this

 

point.

 

 

Use this option only with Fire points to designate them for alarm verification.

When an Alarm Verification point enters into alarm, the control panel removes power to all Resettable points for the duration programmed in A# Verify Time in Section 2.9 Area Parameters on page 36. If the point (or another Resettable point in the area) is still faulted, or returns to a faulted state within 60 sec after the initial verification time reset, an alarm is generated.

During a Fire Walk Test the reset time is

5 sec. The time programmed in A# Verify Time is ignored.

P## Resettable

Default:

 

Refer to the program record sheet

Selection:

 

Yes or No

Yes

 

This point is reset by the Reset

 

 

Sensor? function and during the

 

 

alarm verification sequence.

 

 

 

No

 

This point is not resettable.

 

 

 

To meet UL 864 requirements, set this parameter to Yes for applicable resettable points.

Use this option if this is a Powered point that requires interruption of power to reset a latched alarm condition. The Resettable point option is typically used with smoke detectors and glass break detectors.

When initiated (either through a Fire Walk Test or the keypad’s Reset Sensor? function) or when the remote programming software (RPS) interrupts power to the device for 5 sec, a Sensor Reset report is sent to the central station receiver.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Page 101
Image 101
Bosch Appliances D9412GV2 manual ## Fire Point, ## Resettable

D9412GV2 specifications

The Bosch D9412GV2 is an exceptional dishwasher that stands out in the competitive world of home appliances. Known for its reliability and advanced features, this model offers a blend of cutting-edge technology and user-friendly design that appeals to modern households.

One of the most noteworthy features of the D9412GV2 is its impressive cleaning performance. Boasting a unique combination of powerful jets and specialized wash cycles, it ensures that even the toughest stains are removed effectively. The dishwasher features Bosch’s patented PrecisionWash system, which utilizes intelligent sensors to monitor the wash cycle’s progress and adjust the water spray for optimal cleaning results. This not only guarantees sparkling dishes but also conserves water and energy.

In terms of capacity, the D9412GV2 does not disappoint. It has a spacious interior that is designed to accommodate up to 16 place settings, making it an ideal choice for families or those who frequently entertain guests. The adjustable racks and flexible loading options allow users to maximize space and customize the dishwasher to suit their unique needs. The third rack is particularly useful for utensils and smaller items, providing additional space that enhances efficiency.

The dishwasher is also engineered with noise reduction features for a quieter operation. With a sound rating of 44 decibels, it operates silently in the background, allowing for uninterrupted conversations and a peaceful home environment. This is especially beneficial for open-concept living spaces.

Energy efficiency is another hallmark of the Bosch D9412GV2. It is Energy Star certified, reflecting its commitment to sustainable practices. It uses less water and electricity without compromising performance, making it a responsible choice for eco-conscious consumers.

Moreover, the presence of the Home Connect feature allows users to control and monitor their dishwasher remotely via a smartphone app. This innovative technology enables users to start or stop cycles, receive notifications, and even download new wash programs, adding convenience and flexibility to busy lifestyles.

In conclusion, the Bosch D9412GV2 is a state-of-the-art dishwasher that excels in cleaning performance, capacity, and energy efficiency. With its innovative technologies and thoughtful design, it represents Bosch's commitment to quality and customer satisfaction, making it a valuable addition to any kitchen.