2.5Power Supervision

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 28

Table 21: Event Descriptions, Priorities, and Numbers, continued

 

Event

 

 

Priorit

Event

Event Description

y

Number

Parameters Changed

008

054

RPS Access OK

008

064

RPS Access Fail

008

065

Remote Reset

008

079

 

 

 

Program Access OK

n/a

n/a

Program Access Fail

n/a

n/a

Service Start

008

029

Service End

008

030

Fire Walk Start

008

036

Fire Walk End

008

037

Walk Test Start

008

038

Walk Test End

008

039

Extra Point

008

023

Send Point Text

n/a

n/a

RF Low Battery

006

093

RF Battery Restore

006

094

Date Changed

008

059

Time Changed

008

060

Delete User

008

090

User Code Change

008

056

Area Watch

008

042

Card Assigned

008

110

Change Level

007

061

Access Granted

008

003

No Entry

008

115

Door Left Open

008

116

Cycle Door

008

112

Door Unlocked

008

113

Door Secure

008

114

Door Request

008

117

Door Locked

008

145

User Alarm COMMAND 7

002

005

User Alarm COMMAND 9

002

006

2.5Power Supervision

AC Fail Time

Default: 1

Selection: 1 to 90 (Blank and 0 are invalid)

Program the amount of time that AC power must be off before the control panel responds to the AC failure. The response to restoral of AC power is delayed for the same amount of time. The control panel always monitors AC. The response to this prompt is the actuation of the relay programmed in the Panel-Wide Relays prompt AC Failure (refer to Section 2.13.2 Panel-Wide Relays on page 81) and the AC Fail report enabled by the AC Fail/Res Rpt prompt. Local annunciation of an AC failuter is controlled by the AC Fail Display prompt.

UL 864 requirements, Section 50.2.1.b states: “A trouble signal shall be transmitted for remote station, central station, and proprietary-type protected premises units after a delay of between 60 and 180 min.

Exception: Products are not prohibited from providing capability of selecting that the primary power failure trouble signal transmission be delayed other time periods, including no delay,provided the 60 – 180 min delay is also included.”

To meet UL 864 requirements, program AC Fail Time with 61, 63, 65, ... (odd numbered values), and 89. Always check with the Authority Having Jurisdiction for local requirements.

When you program AC Fail Time, if the second digit is:

1, 3, 5, 7, or 9 (such as 3, 5, 11, 13, 15, 21, and so on): The AC Fail Time interval is in minutes.

2, 4, 6, 8, or 0 (such as 2, 4, 6, 10, 12, 20, 22, and so on): The AC Fail Time interval is in seconds.

For the following items to be true, AC Fail/Res Rpt must be programmed as Yes and AC Tag Along must be programmed as No.