Bosch Appliances D9412GV2 manual P## Supervised, P## Scope, P## A1 through A8 in Scope

Models: D9412GV2

1 158
Download 158 pages 17.38 Kb
Page 31
Image 31
P## Supervised

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 31

P## Supervised

Default:

No

Selection:

Yes or No

Yes

Only one printer can be installed for

 

this P## SDI address.

 

 

No

More than one unsupervised printer

 

can be installed using this P## SDI

 

address and the same address DIP

 

switch setting.

 

 

Supervise this SDI address. Generate Trouble SDI

##Reports and local trouble annunciation if a problem occurs with this printer or the SDI bus.

Unsupervised printers sharing the same address setting print the same text.

Trouble SDI ## Reports are always reported as Area 1, Account 1 Events regardless of where the SDI device is assigned.

When P## Supervised is set to Yes and all Printer Event Groups (such as P## Fire Events, P## Burglar Event, or P## Usr Chng Evt) are set to No, the control panel does not generate Trouble SDI ## Reports for the printer if the D9131A becomes disconnected.

P## Scope

Default:

No Printer

Selection:

No Printer, Area, Account, Panel

 

Wide, Custom

Panel

Printer prints all designated events

Wide

that occur panel-wide. A panel-wide

 

printer can cross account boundaries.

 

 

Account

Printer prints all designated events

 

that occur within any area with the

 

same account number in which this

 

printer is assigned.

 

 

Area

Printer prints all designated events

 

that occur in the area to which this

 

printer is assigned.

 

 

Custom

Printer prints all events occurring in

 

areas programmed Yes for this

 

prompt regardless of any boundary

 

restrictions.

 

 

No Printer

No printer installed at this address. If

 

a printer is connected, data does not

 

print.

 

 

Press the [SPACE] bar to scroll through the selections. Press [ENTER] when the correct selection appears in the display.

The following prompts are visible only when you program P## Scope to Custom.

P## A1 [through A8] in Scope

Default:

No

Selection:

Yes or No

Yes

Include Area # Events in the scope of

 

this printer.

 

 

No

Does not include Area # Events in

 

the scope of this printer.

 

 

Only available if P## Scope is programmed Custom. This program item determines if events occurring in an area print at this printer.

Refer to the report tables in Section 2.3 Routing on page 15 to identify the events that print. Events programmed as No in Routing still print at the local printer. Individual events within the report group cannot be suppressed for events printed at the local printer.