Bosch Appliances D9412GV2 manual CC# Entr Cycl Dr, CC# Assign Door, Default, Selection, Yes or No

Models: D9412GV2

1 158
Download 158 pages 17.38 Kb
Page 53
Image 53
CC# Entr Cycl Dr

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 53

When programmed to activate a relay, the [ENTER] key cannot be used for any other function.

Relays used for this function must not be shared with any other point, sensor reset, control panel, or bell functions. Sharing can cause errors in relay operation.

CC# Entr Cycl Dr

Default:

No

Selection:

Yes or No

Yes

The [ENTER] key is used to cycle the

 

door programmed for CC Assign

 

Door.

 

 

No

The [ENTER] key is not used to cycle

 

the door.

 

 

Enter Key Cycle Door: Program this prompt as Yes to start the door cycle sequence for the door number programmed in CC# Assign Door when a user enters a valid pass code and presses [ENTER]. This includes shunting the point assigned to the door. ACCESS GRANTED prints on the local printer and at the central station receiver, if programmed.

• The service pass code cannot be used for the CC# Entr Cycl Dr application.

When programmed to activate a relay, the [ENTER] key cannot be used for any other function.

Relays used for this function must not be shared with any other point, sensor reset, control panel, or bell functions.

Sharing can cause errors in relay operation.

The door does not cycle if Entr Key Rly is programmed.

9210 NOT READY appears at this keypad when you press [ENTER] if the D9210B is not programmed with a D# Entry Area (in the RADAXS handler) or if CC Assign Door does not have a door number assigned.

CC# Assign Door

Default: Blank

Selection: 1 to 8, Blank

Blank

No door controller is assigned for adding

 

tokens or the CLOSE DOOR # appears on

 

the keypad.

 

 

1 to 8

The door controller assigned to this keypad

 

is used to read new tokens when the Add

 

User Mode is initiated.

 

 

If the assigned door remains open and this keypad has the CC# Close Door Warning Tone set to Yes, the CLOSE DOOR # message appears on this keypad.

• If a door is not programmed for this prompt and a door is not assigned to the area using the D# Entry Area in the RADAXS handler, 9210 NOT READY appears at this keypad when you attempt to add a user. The message indicates that the control panel cannot start the Add User Mode until a door is assigned to this keypad.

Assigning a door to a keypad is not necessary for the user to control the door(s) using the Door Control function. Any door that is active can be controlled by a user who has the appropriate door control authority. The door control functions are available to a valid user at any keypad with access to the area where the door is assigned.

During the Add User Mode, tokens or cards, door control requests, and RTE/REX do not function. Put the Door Mode into an unlocked state before adding users if there is heavy activity for this door.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Page 53
Image 53
Bosch Appliances D9412GV2 manual CC# Entr Cycl Dr, CC# Assign Door, Default, Selection, Yes or No