A# Alarm Bell

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 79

Relay functions that resume the proper state within one minute:

Alarm Bell

Perimeter Fault

Summary Fire

Summary Trouble

Area Armed

Reset Sensors

Fire Bell

AC Fail

Summary Alarm

Phone Fail

Silent Alarm

Summary SupBurg

Area Fault

Battery Trouble

Summary Fire Tbl

Communications Fail

Watch Mode

Summary SupFire

Relay functions that must be reset manually with Change Relay function (COMMAND 54):

Fail To Close

Force Armed

Duress

Log % Full

2.13.1 Area Relays

Each area can be assigned a unique relay number for each of the events listed in this section.

Area

Default: 1

Selection: 1 to 8

Enter the area number you are programming.

A# Alarm Bell

Default: A

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

This voltage output relay activates and provides

12 VDC output when a Non-fire point (P## Fire is No) assigned to this area activates an alarm.

A# Burg Time and A# Burg Pat must be programmed in Area or Bell Parameters. This relay activates according to the bell pattern and remains active until the bell time expires or a valid passcode is entered. P## Silent Bell must be No for the bell to ring upon alarm.

For SIA CP-01 Compliance:

Do not set A# Alarm Bell to blank. This feature is required for SIA CP-01 compliance.

A# Fire Bell

Default: A

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

This voltage output relay activates and provides

12 VDC output when a Fire point (P## Fire is Yes) assigned to this area activates an alarm.

Fire Time and Fire Pat must be programmed in Bell Parameters. This relay activates according to the bell pattern and remains active until the bell time expires. P## Silent Bell must be No in order for the bell to ring upon alarm.

Although Relay C is a valid entry for A# Fire Bell, do not program Relay C for this entry. Use Relay A for the A# Fire Bell.

To meet UL 864 requirements, set A#

Fire Bell to a value other than Blank.

A# Reset Sensors

Default: C

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

Unlike the default relay for Alarm Bell and Fire Bell, this voltage-output relay (Relay C) de-activates for

5 sec when the Reset Sensors? function is activated from the keypad or during a Fire Walk Test.

The Reset Sensors time converts from the

5 sec default time to the time programmed in A# Verify Time (Section

2.9Area Parameters on page 5) when a point programmed for P## Alarm Verify (Section 4.1 Point Index on page 88) enters an alarm condition.