A# Fire Time

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 42

Area

Default: 1

Selection: 1 to 8

Enter the area number you are programming.

A# Fire Time

Default:

6 min

Selection:

1 min to 90 min

 

 

Enter the number of minutes the bell rings for Fire Alarm points. The relay activated for this time is programmed in A# Fire Bell in Area Relays.

The bell output begins as soon as the fire alarm occurs. It shuts off the bell when the programmed number of minutes expires.

If programmed for 1 min, the output can be anywhere from 0 to 60 sec of bell time. Program Fire Time for 2 min or more to ensure you have ample output time.

To meet UL 864 requirements, program A# Fire Time for at least 5 min. Check with your AHJ to determine the appropriate bell time for your geographical area.

A# Fire Pat

Default:

Pulse

Selection:

Steady, Pulse, CaStnd, TmCod3

Steady

Steady Output

 

 

Pulse

Pulse March Time

 

120 beats per minute, at an even

 

tempo

 

 

CaStnd

California Standard

 

10 sec On + 5 sec Off + 10 sec On +

 

5 sec Off. This sequence repeats

 

until bell time expires.

 

 

TmCod3

Temporal Code 3

 

0.5 sec On, 0.5 sec Off, 0.5 sec On,

 

0.5 sec Off, 0.5 sec On, 1.5 sec Off;

 

pattern repeats. This sequence

 

repeats for a minimum of 3 min and

 

with a ± 10% tolerance.

 

 

Select the bell pattern this area uses to signal an alarm on a Fire point.

Press the [Space] bar to scroll through the selections. Press [Enter] when the correct selection appears in the display.

When an alarm occurs on two Fire points sharing the same relay, the bell pattern of the most recent fire event takes precedence.

A# Burg Time

Default: 6 min

Selection: 1 to 90 min (in one-minute increments)

4 min for UL

5 min for ULC

Enter the number of minutes the bell rings for Burglary Alarm points. The relay activated for this time is programmed in A# Alarm Bell in Area Relays.

The bell output begins as soon as the burglary alarm occurs. It shuts off the bell when the programmed number of minutes expires.

When the control panel’s internal clock begins a new minute, it considers the first minute expired. Program Burg Time for 2 min or more.

Check with your AHJ to determine the appropriate bell time for your geographical area.

For SIA CP-01 Compliance:

A# Burg Time must be 6 min or more.

A# Burg Pat

Default: Steady

Selection: Steady, Pulse, CaStnd, TmCod3

Select the bell pattern this area uses to signal an alarm on a Non-fire point.

Press the [SPACE] bar to scroll through the selections. Press [ENTER] when the correct selection appears in the display.