Bosch Appliances D9412GV2 manual 2.9Area Parameters, Cancel Report, A# Area On, A# Acct Number

Models: D9412GV2

1 158
Download 158 pages 17.38 Kb
Page 36
Image 36
Cancel Report

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 36

Cancel Report

Default:

No

Selection:

Yes or No

Yes

Send Cancel and Fire Cancel

 

Reports according to routing.

 

 

No

Do not send Cancel and Fire Cancel

 

Reports.

 

 

A Cancel and Fire Cancel Report is created when a passcode is entered to silence an Alarm Bell or a Fire Bell before the bell time expires.

For SIA CP-01 Compliance

This prompt must be set to Yes.

2.9Area Parameters

This programming module contains three programming categories: Area Parameters, Bell Parameters, and Open/Close Options.

2.9.1Area Parameters

Area

Default: 1

Selection: 1 to 8

Enter the area number you are programming.

A# Area On

Default:

Yes (Area 1 only)

Selection:

Yes or No

Yes

Enable area.

 

 

No

Disable area.

 

 

Use this program item to enable or disable the area specified.

Area 1 must be enabled:

• System events such as power and phone supervision do not send a report correctly if Area 1 is disabled.

When programmed No, points assigned to this area do not generate events, show at the keypad when arming and disarming, or send status reports. All user authority in this area is turned off while the area is disabled.

To meet UL 864 requirements, set A#

Area On to Yes.

A# Acct Number

Default: 0000

Selection: For BFSK: 0000 to 0999, 0BBB to 0FFF

For Modem (four-digit account numbers): 0000 to 9999, BBBB to FFFF

For Modem (ten-digit account numbers): 0000000000 to 9999999999, BBBBBBBBBB to

FFFFFFFFFF

Determines the account number for this area. An account number must be assigned to each active area.

Account numbers are used to group areas together. Each area can have a different account number, or several areas can share the same account number. The control panel uses the account number as a reference for arming and keypad text displays.

BFSK: Only the last three digits are sent. Insert a 0 as the first digit of the account number.

Example: 0 2 3 4.

Modem IIIa2: Enter a four-digit or ten-digit number.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Page 36