Battery Trouble

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 82

Battery Trouble

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

Activates when battery voltage falls below 85% of capacity (12.1 VDC) for a fully charged (13.8 VDC) battery, or when the battery is in a missing condition. This relay automatically resets when battery power restores.

Use this relay to create audible annunciation. Enable the keypad’s trouble sounders for all applications except commercial fire systems.

Phone Fail

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

Activates when a telephone line failure occurs. A time must be entered in Ph Supv Time (refer to Section 2.2 Phone Parameters on page 12) for this relay to activate. This relay resets automatically when restoral of the phone line(s) occurs.

Comm Fail

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

Activates when a control panel cannot communicate a report after making ten attempts to each routing destination. At the same time, COMM FAIL RT ## displays at the keypad. This relay automatically resets when a report is sent successfully.

Use this relay to report primary digital report failure to an alternate communication device.

Log % Full

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

Enter the number of the relay that activates when the log reaches the programmed percentage of its capacity as programmed in the Log % Full prompt under GV2MAIN. This relay provides a steady output until a Get Log and Set Pointer is executed from the remote programming software (RPS).

Summary Fire

Default: Blank

Selection Blank, 1 to 128 (1 to 64 for

:D7412GV2), A, B, or C

Enter the number of the relay that activates when any Fire point in the system (P## Type 0, P## Fire Yes) enters into alarm. This relay provides a steady output until all Fire points in the system return to normal. Refer to Fire Summary Sustain on page 139 for details on alternate operation.

Summary Alarm

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

Enter the number of the relay that activates when a Non-fire point enters into alarm. This relay provides a steady output until the alarm is acknowledged by a valid pass code, then cleared from alarm memory with an acknowledgment at the keypad.

This relay does not activate for silent and invisible alarms.

Summary Fire Tbl

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

Activates when any Fire point in the control panel is in trouble, or if a Fire Supervision point is missing. This relay provides a steady output until all Fire points restore to a normal condition.

Summary SupFire

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

Activates when any Fire Supervisory point in the control panel is in a supervisory condition (off- normal). This relay provides a steady output until all Fire Supervisory points are restored to a normal condition.