Models: D9412GV2

1 158
Download 158 pages 17.38 Kb
Page 9
Image 9
Settings Permitted in UL 864

D9412GV2/D7412GV2 Program Entry Guide 1.0 Introduction

EN 9

Table 5: UL 864 Programming Requirements (continued)

Product Feature/Option

Permitted in

Possible Settings

 

UL 864? (Y/N)

 

Area 1 Area On

Required to

Yes / No

 

send system

 

 

status reports

 

A# Delay Res

Yes

Yes / No

Verify Time

Yes

10 to 60 sec

Area # Fire Time

Yes

1 to 90 min

CC# Supervised

Yes

Yes / No

CC# Trouble Tone

Yes

Yes / No

CC# Scroll Lock

Yes

Yes / No

Remote Program

Disable /

Blank, E, or P

 

Enable

 

A# Fire Bell

Yes

A,B,C, 1 to 128,

 

 

Blank

A# Reset Sensors

Yes

A,B,C, 1 to 128,

 

 

Blank

U### Area # Auth

Yes

1 to 8, Blank

 

 

 

U### Passcode

Yes

3-, 4-, 5-, or 6-digit

 

 

passcode

P## Silent Bell

No

Yes / No

P## Invisible Pt

No

Yes / No

P## Local While

No

Yes / No

Disarmed

 

 

P## Local While Armed

No

Yes / No

P## Disable Rst

No

Yes / No

P## Bypassable

No

Yes / No

P## Swinger Byps

No

Yes / No

P## Fire Point

Yes

Yes / No

P## Resettable

Yes

Yes / No

Sked## Function Code

Required

1 to 11, 13 to 28

Sked## Defer Test

No

Yes / No

Sked## Hourly Test

No

Yes / No

(Report?)

 

 

Sked## Time

Enter valid time

00:00 to 23:59

Sked## Date

No

mm/dd

Sked## Sunday

Yes

Yes / No

Sked## Monday

Yes

Yes / No

Sked## Tuesday

Yes

Yes / No

Sked## Wednesday

Yes

Yes / No

Sked## Thursday

Yes

Yes / No

Sked## Friday

Yes

Yes / No

Sked## Saturday

Yes

Yes / No

Sked## Xept On Holiday

No

Yes / No

Settings Permitted in UL 864

Set to Yes

Set to Yes 60 sec

5 min (check with AHJ) Set to Yes

Set to Yes

Set to Yes

Set to P

Program with a relay

Program with a relay

Program an Authority Level for the Fire Area

Must program at least one passcode

Set to No

Set to No

Set to No

Set to No

Set to No

Set to No

Set to No

Set to Yes

As required

Sked Function Code 9 Set to No

Set to No

00:00 to 23:59 Set to No Set to Yes Set to Yes Set to Yes Set to Yes Set to Yes Set to Yes Set to Yes Set to No

Refer to Page:

36

38

38

42

51

54

56

65

79

79

85

86

94

95

97

98

98

99

100

101

101

116

118

118

123

123

123

123

123

123

123

123

123

124

Bosch Security Systems, Inc. 10/08 F01U003636-04

Page 9
Image 9
Bosch Appliances D9412GV2 manual En, Product Feature/Option, Permitted in, Possible Settings, UL 864? Y/N, Refer to Page