Bosch Appliances D9412GV2 4.3Point Assignments, P## Alarm Abort, Point Number, P### Point Index

Models: D9412GV2

1 158
Download 158 pages 17.38 Kb
Page 102
Image 102
P## Alarm Abort

D9412GV2/D7412GV2 Program Entry Guide 4.0 RADXPNTS

EN 102

When a sensor reset occurs, the control panel does not accept alarms from any points with P## Resettable programmed as Yes. During the 5-sec reset time, alarms from these points are ignored.

Do not mix fire and intrusion devices on the same powered loop.

P## Alarm Abort

Default:

Yes

Selection:

Yes or No

Yes

If the point goes into an alarm

 

condition, the system delays the

 

alarm report for the amount of time

 

specified in the control panel-wide

 

parameter Abort Window.

 

 

No

If the point goes into an alarm

 

condition, alarm reports are sent

 

immediately.

 

 

This parameter allows points with the associated Point Index to delay a Burglar Alarm (non-fire) event for the time period specified in the Abort Window. An alarm is aborted by performing an alarm silence operation at a keypad showing the burglar alarm condition before this time elapses.

When an alarm is successfully aborted, the keypad shows an optional ALARM NOT SENT message and no event is sent or written in the control panel event log. Refer to CC# Abort Display on page 56.

For SIA CP-01 Compliance:

P## Alarm Abort can be set to Yes or No.

This feature does not apply to Fire Alarms or invisible point alarms.

4.3Point Assignments

These entries assign point indexes to Points 1 to 127, 129 to 247 for the D9412GV2 and Points 1 to 75 for the D7412GV2, and assign the points to the areas. Also included in this section are parameters used to set the point’s debounce count, BFSK/Relay (for use when transmitting in BFSK or assigning relays to follow alarms for a group of points), and custom keypad and report text for each point.

Point Number

Default: 1

Selection: 1 to 127, 129 to 247

Enter the point number you are programming. When transmitting in Modem IIIa2, the three-digit point number is reported to the D6500 or D6600. When transmitting in BFSK, you must assign a zone number in BFSK/Relay.

Point number 128 is reserved for supervising Zonex 1.

Point number 248 is reserved for supervising Zonex 2.

P### Point Index

Default:

 

Refer to the program record sheet

 

 

 

Selection:

 

Blank (00) to 31

 

 

 

This entry selects one of the 31 P## Index codes that define the point’s characteristics and determines how the control panel responds to various point conditions.

Blank (00) disables the point.

Missing Point Report

If a Point Index is assigned to a point that has an incorrect address or that is not connected to the point bus, a Missing Point Report occurs.

When a POPIT is missing, the control panel generates the following responses based on the point type:

• Fire points generate missing trouble responses.

Non-fire 24-hour points generate missing alarm responses.

Non-fire, non 24-hour points generate missing

alarm responses while armed, and trouble responses while disarmed. Exception: Non-fire, non-24-hour points with a point response of 9 to D generate a missing alarm response while disarmed.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Page 102
Image 102
Bosch Appliances D9412GV2 4.3Point Assignments, P## Alarm Abort, Point Number, P### Point Index, parameter Abort Window