Bosch Appliances D9412GV2 manual A# Duress Enable, Verify Time to 60 sec

Models: D9412GV2

1 158
Download 158 pages 17.38 Kb
Page 39
Image 39
Verify Time to 60 sec.

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 39

When an Alarm Verification point senses an alarm, the control panel automatically removes power to all Resettable points connected to the area’s Reset Sensors relay. The sensor reset removes power to the sensors for the amount of time programmed in Verify Time. When power is reapplied, a 60-sec confirmation window begins. If the detector is still in alarm and experiences another alarm during the confirmation window, or a different Resettable Verification point in the area senses an alarm, an alarm occurs.

Example: Verify Time is set for 20 sec. The alarm verification cycle starts when the detector senses smoke or fire. No report occurs.

When the detector senses smoke or fire, the area’s sensor reset relay interrupts power to points connected to it for the time in Verify Time.

When power restores to the points, the 60-sec confirmation window starts. If any detector, reset during the verification time, experiences another alarm during the confirmation window, an alarm occurs. If there is no activity during this period, no alarm occurs and the verification window ends. If a Verification point senses another alarm after the window ends, a new verification cycle begins. Refer to Table 24 for an example of Verify Time.

To meet UL 864 requirements, set A#

Verify Time to 60 sec.

Table 24: Verify Time

 

Verification Point

Verify Time/Reset

60 sec

Restart Alarm

 

Activiation

Sensors

Confirmation

Verification Cycle if

 

 

 

Power removed,

Generate alarm if

an Alarm

 

 

 

ignore activity

additional activity

Verification point

 

 

 

 

received.

activates.

Example: Total

*

 

20 Sec

60 Sec

 

Cycle time 80 sec

 

 

 

 

 

 

 

 

 

 

A# Duress Enable

Default:

No

Selection:

Yes or No

Yes

Enable Duress alarm for this area.

 

 

No

Disable Duress alarm for this area.

 

 

Refer to Duress Type in Section 2.8 Miscellaneous on page 35 for an explanation of duress.

The passcode you normally use for duress is not valid in an area with A# Duress Enable set to No.

If a passcode with the appropriate

L# Disarm authority is used to duress disarm an area with A# Duress Enable set to No, NO AUTHORITY appears in the display. Also, if the keypad display is moved to an area with A# Duress Enable set to No using [COMMAND][5][0], a valid duress disarm passcode does not send a duress report.

For SIA CP-01 Compliance:

A# Duress Enable must be set to Yes.

Bosch Security Systems, Inc. 10/08 F01U003636-04