4.2Point Responses

D9412GV2/D7412GV2 Program Entry Guide 4.0 RADXPNTS

EN 92

4.2Point Responses

4.2.1Applications for Point Responses 9, D, and E:

Combine Point Responses 9, D, and E with Perimeter point types to create more flexible 24-hour protection. Unlike 24-hour points, a faulted Perimeter point with a Point Response of D and E displays at the keypad when arming. Like a 24-hour point, a point programmed this way can generate alarms whether the area is armed or disarmed.

Combining Point Response 9 with the Local While Disarmed feature provides off-site reporting when the area is armed, but only local alarm annunciation when the area is disarmed.

Combining Point Response 9 with the Local While Armed feature provides off-site reporting when the area is disarmed, but only local alarm annunciation when the area is armed.

Point Response E: Use this setting for Zonex or ASIC motion detectors. The control panel can report troubles while Master Armed.

Point Response F: Does not sound at local keypads but activates P## RlyResp Type 1 and keypad faults. To annunciate the off-normal state at a keypad, program Disp as Dvc as Yes and optionally set BuzzOn Fault as 1 or 2. This point response does not generate alarms or activate an alarm relay.

Point Response 8, 9, A, B, and C: These point responses provide supervisory (24-hour) reporting.

4.2.2Characteristics of a Fire Point:

Reporting: When a group of events occurs, the control panel routes and prints out Fire Reports first.

Visual Annunciation: FIRE TROUBLES continues to scroll until the trouble clears. When acknowledged, a FIRE TROUBLE scroll notifies the end user that a Fire point, or group of Fire points, is still in trouble. Panel-Wide Relays, Summary Fire, and Summary Fire Tbl activate if a relay is assigned when any Fire point enters into alarm or is in trouble.

Audible Annunciation: A Fire point activates the A# Fire Bell relay programmed in Relay Parameters. The amount of time and the pattern of the relay activation is programmed by area in Bell Parameters, A# Fire Time, and A# Fire Pat.

Supervisory: A Fire point can send a Fire Supervisory Report and activate the Summary Fire Sup and Summary Fire Tbl, Panel-Wide Relays with a

P## Response of 8-9-A-B-C.

Alarm Verification: A Fire point can delay an alarm by the length of time programmed in A# Verify Time in the Area Parameters. Combined with A# Resettable, a Fire point also resets the electrical circuit for the amount of time programmed.

Reset Sensor: A fire device that requires resetting can be manually reset using the reset sensor relay for the area to which it is assigned.

Fire Walk: Use the Fire Walk function to test Fire points in the system. The Fire Walk Test automatically resets each point for 5 sec when the point is activated, and rings the Fire Bell for 2 sec.

To provide an audible tone for a restored Fire Supervisory point, use P## RlyResp Type 1 and connect the corresponding relay to a visual annunciator.