2.7.2Log Threshold Reports

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 33

2.7.2Log Threshold Reports

If communication with RPS is unsuccessful, or if no phone number is programmed in RPS Ph, the control panel generates Log Threshold and Bad Call to Ram. This indicates the log is filling and the control panel cannot download its events.

If there is no RPS Ph programmed, the control panel generates the Log Threshold and Bad Call to RPS Events immediately. Bad Call to RPS Events are logged only locally. If an RPS Ph is programmed, the control panel makes multiple attempts to reach RPS before sending the reports. Refer to the RPS Ph prompt in Section 2.7.3 RPS Callback Reports for an explanation of dialing characteristics.

2.7.3RPS Callback Reports

When dialing the RPS phone number, the control panel makes two attempts to reach RPS. If the control panel does not reach RPS on the first two attempts, it waits 10 min then tries six more times with a 10-min interval between each attempt. One hour after the last failed attempt, the control panel starts dialing the RPS phone number again. It makes two more attempts then waits 10 min and tries six more times with 10-min intervals between each attempt before generating a Bad Call to RPS Report and abandoning the effort.

Remote Program Dialing Exception: When an RPS phone number is programmed, the user can call RPS by entering [COMMAND][4][3] and pressing the [NEXT] key until CALLRPS? is displayed. Press [ENTER]. Only one attempt is made to contact RPS.

RPS Passcode

Default: 999999

Selection: 0 to 9, A to F

(six characters required)

Enter six characters. Do not use a space in the passcode.

The control panel verifies the remote programming software at the central station has valid access before connecting using the RPS passcode.

Log % Full

Default: Blank

Selection: 1 to 99, or Blank

This parameter determines how full the memory log can be before initiating a call to RPS at the central station. This allows the central station to call the control panel and copy the memory log before messages are overwritten.

Blank disables the Log Threshold and Log Overflow Events. These events are not entered in the log or reported to the D6500 or D6600 or the local printer.

The control panel continues to log events after the Log Threshold Report is sent. When it reaches 100% capacity (memory logger is full and previously stored events are overwritten), the control panel generates a local Log Overflow Event.

The control panel does not call RPS again until it downloads the log and the Log % Full percentage is reached. These events are also sent to the control panel’s event log and to the local printer(s) if installed.

The Log Overflow Event is not sent to the central station unless Expanded Test Rpt is programmed Yes.

Failure to program the RPS telephone number results in a BAD CALL TO RPS trouble event sent to the central station when the log threshold is reached. Refer to the RPS Ph prompt on page 35 for information about programming the RPS telephone number.