D# Door Point

D9412GV2/D7412GV2 Program Entry Guide 7.0 RADXAXS

EN 145

Table 44: Effects of Programming on Custom Function Activation

 

L## Function

Custom Function Activation

 

Level?

 

 

M

User token activates the custom

 

(Armed)

function assigned to the Door

 

 

 

Controller only while the entry area

 

 

 

for the Door Controller is Master

 

 

 

Armed or Perimeter Armed.

 

D

User token activates the custom

 

(Disarmed)

function assigned to the Door

 

 

 

Controller only while the entry area

 

 

 

for the Door Controller is disarmed.

 

C

User token activates the custom

 

(Armed and

function assigned to the Door

 

Disarmed)

Controller regardless of the armed

 

 

 

state of the entry area.

 

Blank

User token does not run the custom

 

 

 

function assigned to the Door

 

 

 

Controller.

 

 

 

 

 

 

 

 

 

 

 

 

A user’s security level must have an M,

P, or D to operate the custom function.

D# Door Point

Default:

Blank

Selection:

Blank, 1 to 127, 129 to 247

1 to 127,

The point number assigned to this

129 to 247

door. Points 128 and 248 are

 

reserved by the control panel for

 

internal use.

 

 

Blank

No point number is assigned to this

 

door.

 

 

Enter the point number assigned to this door. This point cannot be used for any other point assignments.

Door points must be programmed as Perimeter points. If a 24-hour point type is required for the Door point, you can use a Perimeter point type with a point response of 9 to C. Also, the debounce count must be set to 4 in Point Assignments.

When assigning Points 1 to 8 (control panel zones), the end-of-line (EOL) resistors must be removed from the control panel.

Also, do not enable any POPIT points (or OctoPOPIT points) sharing the same point number as the Door point. Failure to do so results in extra point trouble conditions upon reboot.

D# Interlock Point

Default:

 

Blank

Selection:

 

Blank, 1 to 127, 129 to 247

1 to 127,

 

The point number assigned to the

129 to 247

 

Interlock point. Points 128 and 248

 

 

are reserved by the control panel for

 

 

internal use.

 

 

No point number is assigned to the

Blank

 

 

 

Interlock point.

 

 

 

Enter the interlock point number. This point, when faulted, prevents the door controller from allowing access upon a valid ID read or door request.

Do not assign this point to another D# Door Point. You can, however, assign it to another controller to prevent multiple controllers from activating.

Door points must be programmed as Perimeter points. If a 24-hour point type is required for the Door point, you can use a Perimeter point type with a Point Response of 9 to C. Also, the debounce count must be set to 4 in Point Assignments.

The Interlock point is considered in a normal state if it is bypassed, swinger bypassed, or forced armed. This results in normal access even if the door remains open.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Page 145
Image 145
Bosch Appliances D9412GV2 manual D# Door Point, D# Interlock Point, Default, Selection, Blank, 1 to 127, 129 to