A# Force Armed

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 80

When sharing one relay to reset sensors in two or more areas, you must program the following. Failure to do so causes TROUBLE PT ### for all point types programmed as P## Resettable.

CC # Scope must include all areas that share the relay.

L## Reset Sensors authority must be assigned to the pass code that activates the COMMAND 47 or Reset Sensor function.

A# Verify Time must be the same number of seconds for all areas that share the relay.

To meet UL 864 requirements, set A#

Reset Sensors to a value other than

Blank.

A# Fail to Close

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

This relay activates when the Closing Window expires for the specified area. It remains active until midnight, another Closing Window starts, or the control panel resets, whichever occurs first. When Perimeter Relay (refer to page 142) is set to Yes, the A# Fail to Close prompt becomes A# Perimeter Relay when using firmware version 7.07 and later. Refer to Area 7 in Alternate Functions for A# Silent Alarm on page 81 for additional relay functions when using firmware version 7.06 and earlier.

A# Force Armed

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

This relay activates when this area is Force Armed. It remains active until the area disarms or the control panel resets.

If Force Bypassing is required during Perimeter Arming, this relay does not activate.

A# Watch Mode

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

This relay activates when a Controlled point programmed for P## Watch Point is faulted in the specified area while the area is in Watch Mode and the point is not armed. It remains active for 2 sec after each point is faulted.

A# Area Armed

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

This relay activates when the specified area becomes Master Armed. The exit delay must expire before the relay activates. The relay remains active until the area disarms. It does not deactivate during the entry delay time.

If multiple areas use the same relay, the relay activates when all areas are armed. It deactivates when the first area disarms.

The A# Area Armed relay function can provide visual feedback at a key switch station. Attach a LED to the output of a D8129 Module programmed for this function.

Refer to Area 7 and Area 8 in Alternate Functions for A# Silent Alarm on page 81 for additional relay functions when using firmware version 7.06 or earlier.

A# Area Fault

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

Activates whenever a controlled (P## Type 1, 2, 3 only) Perimeter or Interior point is faulted. The relay remains active until all Perimeter and Interior points in the area are normal.

Keyswitch area armed status with LEDs: Use a D8129 Module and connect an LED to indicate that the area is not ready to arm.