1.3Guide to Programming Options

D9412GV2/D7412GV2 Program Entry Guide 1.0 Introduction

EN 7

1.3Guide to Programming Options

This guide is set up in a specific order. Related program entries are grouped together in modules as they appear in the specific product handlers. The handler and the programming module are listed at the top of each page to help you find specific programming prompts.

This guide shows the programming options for each product handler. Each option is listed with:

The Program Item Prompt: Each prompt is shown as it appears in the D5200 Programmer [refer to the D5200 Programmer Operation Manual.(P/N: 74-06176-000)] or the Remote Programming Software (RPS). Refer to the RPS Installation and Operation Guide (P/N: 4998141259). For space considerations, some prompts must be abbreviated in the Programmer display. In these cases, the meaning of the prompt is explained below the prompt

Program Entry Default Setting: Because defaults are set for the typical installation, programming each prompt might not be necessary. Review the default entries in the program record sheet shipped with the control panel to determine which prompts must be programmed.

Program Entry Selections: Only the selections listed can be used for a particular program item.

Program Entry Description: Describes the various entry selections. Read the descriptions carefully to avoid improperly programmed equipment.

Custom Programming: Select custom programming (Yes or No) to expand programming modules within the D5200. Programming Custom as Yes allows parameters for special applications to be visible in the programmer.

1.4Programming the Control Panel with the D5200 Programmer

Caution: Do not connect the D5200 to the PROG connector without closing the reset switch. Doing so causes SDI ## TROUBLE and CALL FOR SERVICE to display on the keypads. Door controllers also activate, depending upon the SDI failure DIP switch setting.

To acquire an update for your D5200 Programmer, call the Bosch Security Systems, Inc. Handler Update System at

(800)657-4584. Make a separate phone call for each handler.

Use an analog telephone line with the D5200. The D5200 dials only pulses.

Refer to Section 10 Updating Handlers in the D5200 Programmer Operation Manual (P/N: 74-06176-000-B) for details on updating handlers.

To connect the D5200 Programmer to the control panel:

1.Close the reset switch, located in the upper right corner of the control panel and labeled S1 Reset, to place the D9412GV2 or D7412GV2 Control Panel in the standby mode.

2.Connect the Molex® connector at one end of the cord to the connector labeled PROG on the PCB and PROG CONN on the faceplate.

To retrieve the current control panel configuration, press the [RECV (COPY)] key on the D5200 at the NEWRECORD prompt. Refer to the D5200 Programmer Operation Manual (P/N: 74-06176- 000) for detailed information.

To write new configuration information for the control panel, press the [SEND (LOAD)] key at the NEWRECORD prompt. Refer to the D5200 Programmer Operation Manual (P/N: 74-06176- 000) for detailed information.

To disconnect the D5200:

1.Disconnect the the Molex® connector.

2.Open the reset switch.

When the reset switch is opened, the control panel reboots and resumes normal operation within 5 to 25 sec.

Table 4: Programming Error Displays

Display

Description

INCOMPATIBLE

You are connected to the

PANEL

wrong control panel or using

 

the wrong handler. Check the

 

faceplate for the model

 

number and the handler title.

CHECK

Check the cord and the reset

CORD/RESET PIN

pin

 

 