P## RlyResp Type

D9412GV2/D7412GV2 Program Entry Guide 4.0 RADXPNTS

EN 97

P## RlyResp Type

Default:

Refer to the program record sheet

Selection:

Blank, 1 to 2

Blank

Point state does not affect the

 

operation of the corresponding relay.

 

 

1

Relay Follows Point: The relay

 

corresponding with this point

 

activates when the point is faulted to

 

any off-normal condition, even if the

 

point is bypassed. The relay

 

automatically resets when the point

 

returns to normal.

 

 

2

Relay Latches: The relay

 

corresponding with this point latches

 

when the point enters into an alarm

 

condition. This relay provides a

 

steady output until the alarm is

 

acknowledged by a valid pass code,

 

then cleared from alarm memory with

 

an acknowledgment from the keypad.

 

 

Use this option to cause a relay (1 to 127 for D9412GV2; 1 to 64 for D7412GV2) to respond when a corresponding point with the same number (1 to

127)is faulted. This requires connecting D8129 OctoRelays to Zonex Bus 1 and Zonex Bus 2 (D9412GV2 only). Refer to the address settings on the back of the D9412GV2/D7412GV2 Program Record Sheet

(P/N: F01U003635).

Point 128 is reserved for use other than an actual point. Only the first 127 points can have an associated relay. Relays are not available for Points 129 to 247.

Do not use the Chg Relays? function to toggle relays reserved for special functions. Special function relays are Area and Panel Wide Relay functions as well as relays assigned to CC Entr Key Rly and P## RlyResp Type.

P## Disp as Dvc

Default:

 

No

 

 

 

Selection:

 

Yes or No

Yes

 

Display CHECK DEVICE when this

 

 

point is off-normal.

 

 

 

No

 

Do not display CHECK DEVICE

 

 

when this point is off-normal.

 

 

 

Use P## Disp as Dvc to cause the keypad to display CHECK DEVICE when a point is off-normal or is acknowledged after going into alarm.

Use this function for devices with a dry contact output that faults a point when the device is in a trouble condition.

P## Local While Disarmed

Default:

Refer to the program record sheet

Selection:

Yes or No

Yes

Suppress Alarm, Trouble and

 

Restoral* Reports from this point

 

while the area to which it is assigned

 

is disarmed.

 

 

No

Send event reports occurring from

 

this point while the area is disarmed.

*Transmission of Restoral Reports continues if the alarm, trouble, or bypass (by Sked, RPS, or Swinger bypass) condition occurred when the area disarmed, and the point restored.

To meet UL 864 requirements for Central Station and Remote Station applications, set this parameter to No.

Use this option to allow a Controlled point (P## Type 1, 2, 3), to report Alarms, Troubles, and Restoral Reports only when the area is armed. This prompt does not affect local annunciation.