L## Service Walk

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 74

L## Service Walk

Default:

Refer to the program record sheet

Selection:

Blank or E

 

 

 

 

Function

Function Name

Alternate

No.

 

Keystroke

33

Service Walk

(Menu function

 

Test

only)

Start a Service Walk Test for all 24-hour Interior or Perimeter Controlled points in the control panel.

Points are not included in this test if:

Points are in an area that is already in a Walk Test Mode.

Points are assigned to an area that is not enabled A# Area On.

Points are in an area that is Master or Perimeter armed.

When a Service Walk Test is initiated, one person can test all the points in the control panel without assistance. The following features are provided with the Service Test Mode:

Display indicates exactly how many points can be tested.

Battery and bell tests do not occur during this Walk Test.

The test ends when all points are tested or the test times out after 20 min of inactivity.

Events print locally without alarm annunciation or reporting to the central station receiver.

D1255 Keypad displays a sequential count and the text for the point after each point is activated and restored.

The D1255 Keypad displays ALL PNTS TESTED.

If enabled in Routing, Service Start and Service End are reported at the central station receiver for the beginning and end of the test.

Point 128 and Point 248 appear as missing. This is normal. These points are used for supervising the Zonex 1 bus (Point 128) and Zonex 2 bus (Point 248). If the Zonex bus has a fault, these points indicate a short.

This function allows viewing of extra points. Extra points occur under two conditions: an extra point is wired electrically to the Zonex bus with a blank P### Point Index, or two Zonex devices exist for the same Zonex address.

L## Default Text

 

Default:

 

 

Refer to the program record sheet

 

 

 

 

 

 

 

Selection:

 

 

Blank or E

 

 

 

 

 

 

 

 

Function

 

 

Function Name

Alternate

 

No.

 

 

 

Keystroke

 

34

 

 

Default Text

[COMMAND][5][7]

Temporarily show the armed state of the area using control panel default text, A# AREA # IS ON, A# NOT READY, A# AREA # IS OFF, and A# ACCOUNT IS ON.

L## Change Skeds

 

Default:

 

 

Refer to the program record sheet

 

Selection:

 

 

Blank or E

 

 

 

 

 

 

 

 

Function

 

 

Function Name

Alternate

 

No.

 

 

 

Keystroke

 

35

 

 

Change Skeds

[COMMAND][5][2]

Change skeds that can be edited.

Editing of skeds can be restricted by programming S## Time Edit? to No.

L## Invisible Walk Test

 

Default:

 

 

 

Refer to the program record sheet

 

 

 

 

 

 

 

 

 

 

Selection:

 

 

 

Blank, or E

 

 

 

 

 

 

 

Function Name

 

 

 

Function

 

 

 

Alternate

 

No.

 

 

 

 

Keystroke

 

36

 

 

 

Invisible Walk Test

(Menu function only)

Test all points that are programmed to be invisible and that are within the scope of the keypad without sending reports to the central station. Invisible points must be programmed P## Invisible Pt as Yes. This walk test mode can test 24-hour points and controlled points.

Invisible Test? allows the user with this L## to start an invisible walk test for all 24-hour interior and posterior controlled points in the area to which this keypad is assigned. When an invisible test is started, one person can test invisible points without assistance.

The following features are provided with the Invisible Test Mode:

The display indicates exactly how many invisible points are assigned to the area.

Battery and bell tests do not occur during this walk test.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Page 74