CMD9 Point Index

D9412GV2/D7412GV2 Program Entry Guide 4.0 RADXPNTS

CMD9 Point Index

Default: 31

Selection: Blank (00) to 31

This entry selects one of the 31 P## Index codes that define how the control panel reacts when a COMMAND 9 is initiated.

The point index code used for COMMAND 7 and COMMAND 9 must not be used for any other points on the system.

If the point index for COMMAND 9 has Fire points programmed as Yes, this causes access control doors to unlock if Fire Unlock is also programmed as Yes. Refer to the D9210B Program Entry Guide

(P/N: 32207).

CMD9 BFSK/Relay

Default: 1

Selection: 0 to 9

The value in this entry selects one of the digits shown for reporting in BFSK or for activating relays 73 to 80 (on the D9412GV2) or relays 9 to 16 (for the D7412GV2) when a COMMAND 9 is initiated (refer to the P### BFSK/Relay prompt in Section 4.3 Point Assignments on page 103).

COMMAND 9 does not activate the

Summary Fire Alarm relay.

CMD9 Point Text

Default: [COMMAND][9]

Selection: Up to sixteen alphanumeric characters

Enter alphabetic characters (A to Z) in capital letters

Enter up to sixteen characters of text to describe the point. This point text is displayed at keypads (if the point is programmed as visible) and sent to the D6500 or D6600 when transmitting in Modem IIIa2 format (if it is a reporting point).

Bosch Security Systems, Inc. 10/08 F01U003636-04

EN 105