Bosch Appliances D9412GV2 6.7Route Group Attempts, 6.8Miscellaneous, RG# 1 Attempt, RTS Control

Models: D9412GV2

1 158
Download 158 pages 17.38 Kb
Page 139
Image 139
6.7Route Group Attempts

D9412GV2/D7412GV2 Program Entry Guide 6.0 GV2AUX

EN 139

RTS Control

Default:

On

Selection:

On, AutoX, Off, AutoR

On

Sets RTS to on (hardware control).

 

 

Auto X

Automatically enables Xon/Xoff

 

(software control).

 

 

Off

Sets RTS off (hardware control).

 

 

Auto R

Sets this to Auto RTS.

 

 

Determines how the Request To Send (RTS) control parameters are defined for the network interface module (NIM). Pressing the [SPACE] bar on the D5200 toggles through the available options.

Set this item to On when using the

External Modem feature.

DTR Control

Default:

On

Selection:

On, AutoD, Off

On

Sets DTR to on (hardware control).

 

 

AutoD

Sets this to Auto DTR.

 

 

Off

Sets DTR off (hardware control).

 

 

Determines how the Data Terminal Ready (DTR) control parameters are defined for the network interface module (NIM). Pressing the [SPACE] bar on the D5200 toggles through the available options.

Trouble SDI 88 Reports are always reported using the account number for Area 1.

6.7Route Group Attempts

This section determines how many times a route group tries the primary destination before trying the backup destination if the primary destination fails. This entry applies to both Phone numbers and IP addresses.

RG# 1 Attempt

Default:

No

Selection:

Yes or No

Yes

This route group tries the primary

 

destination once and, if

 

unsuccessful, tries the backup

 

destination. The control panel still

 

makes a total of ten attempts (five to

 

the primary, five to the backup)

 

before generating a route group

 

Comm Fail Event.

 

 

No

This route group tries the primary

 

destination twice and, if

 

unsuccessful, tries the backup

 

destination. The control panel makes

 

a total of ten attempts (six to the

 

primary, four to the backup) before

 

generating a route group Comm Fail

 

Event.

Set this item to On when using the

External Modem feature.

9133 Supervision

Default:

No

Selection:

Yes or No

Yes

Supervise the network interface

 

module (NIM).

 

 

No

Do not supervise the network

 

interface module (NIM).

 

 

This item determines whether the NIM is supervised. If the NIM is supervised, disconnecting it from the control panel creates a Trouble SDI 88 Event and the keypad annunciates a trouble tone and displays SERVC SDI 88.

6.8Miscellaneous

Fire Summary Sustain

Default:

No

Selection:

Yes or No

Yes

Forces the Summary Fire relay

 

output to remain on after the Alarm

 

Silence command.

 

 

No

Allows Summary Fire relay output

 

to be silent when the Fire Alarm Bell

 

output is silenced and all Fire Points

 

return to normal.

 

 

Use this parameter to set the Summary Fire relay output to continue or to stop after the Fire Alarm Bell is silenced or times out. Refer to the Summary Fire prompt in Section 2.13.2 Panel-Wide Relays on page 82.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Page 139
Image 139
Bosch Appliances D9412GV2 6.7Route Group Attempts, 6.8Miscellaneous, RG# 1 Attempt, Fire Summary Sustain, RTS Control