Bosch Appliances D9412GV2 2.6Printer Parameters, AC Tag Along, AC/Battery Buzz, Bat Fail/Res Rpt

Models: D9412GV2

1 158
Download 158 pages 17.38 Kb
Page 30
Image 30
AC Tag Along

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 30

AC Tag Along

Default:

Yes

Selection:

Yes or No

Yes

Send AC messages as tag along

 

events.

 

 

No

Do not send AC messages as tag

 

along events.

 

 

Send AC Reports only if any other event occurs while AC is off-normal.

If AC Tag Along is set to Yes and a subsequent event is generated, the AC Fail Event is sent first, before sending any subsequent events.

AC Tag Along is required for NFPA and UL 864 Commercial Fire systems. Be sure to program AC Fail/Res Rpt as No if AC Tag Along is programmed Yes.

AC/Battery Buzz

Default:

No

Selection:

Yes or No

Yes

Initiates panel-wide trouble tone at

 

all keypads.

 

 

No

Does not initiate panel-wide trouble

 

tone at keypads

 

 

Initiates a panel-wide trouble tone at keypads when AC fails or battery is low or missing. This program item does not prevent the SERVC AC FAIL or SERVC BATT LOW displays.

To comply with NFPA standards and

UL 864 requirements for Commercial Fire systems, program this item as Yes.

If annunciating panel-wide troubles at a keypad with CC# Scope set to Panel Wide is undesirable, set CC# Trouble Tone to No. Refer to Section 2.10 Keypad (Command Center) on page 51 for keypad configurations.

Bat Fail/Res Rpt

Default: Yes

Selection: Yes or No

Yes Battery Failure and Restoral Reports are

sent to the central station. They are routed

to the telephone number programmed for

Power/Phone Events.

 

Modem

Missing or

BATTERY

Report

shorted

MISSING

s

Discharged

BATTERY

 

 

below 12.1

LOW

 

VDC

 

BFSK

Missing,

TROUBLE

Report

shorted low

ZONE 9

s

battery

 

No Battery Failure and Restoral Reports are not sent to the central station.

To comply with NFPA standards and

UL 864 requirements for Commercial Fire systems, program this item as Yes.

2.6Printer Parameters

Up to three D9131A Parallel Printer Interface Modules can be connected to the D9412GV2’s (one printer for the D7412GV2’s) SDI bus. Each printer is identified by an address of 17, 18, or 19. Options are available for Routing Reports and area assignments.

Printer Address

Default: 17

Selection: 17, 18, or 19 (only 17 is available for the D7412GV2)

Enter the printer address you are programming.

P## Area Assign

Default: 1

Selection: 1 to 8

Assign an area to the printer programmed in Printer Address.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Page 30
Image 30
Bosch Appliances D9412GV2 manual 2.6Printer Parameters, AC Tag Along, AC/Battery Buzz, Bat Fail/Res Rpt, Printer Address