D9412GV2/D7412GV2 Program Entry Guide 4.0 RADXPNTS

EN 104

Two relays can activate when this point enters into alarm if the P## Rly Resp Type for this point is programmed.

Use these codes to activate relays on the D8129 OctoRelay (or C8137 Transmitter Interface). You can assign the same code to several points providing a summary zone alarm output. When the point enters into alarm, the relay activates. When the alarm is acknowledged and is no longer scrolling in the keypad display, the relay resets.

P### Point Text

Default:

Refer to the program record sheet

Selection:

Up to sixteen alphanumeric

 

characters

 

 

Enter alphabetic characters (A to Z) in capital letters.

Enter up to sixteen characters of text to describe the point. This point text is shown at keypads, if the point is programmed as visible, and sent to the D6500 or D6600 when transmitting in Modem IIIa2 format (if it is a reporting point).

4.4COMMAND 7 and COMMAND 9

These entries assign point indexes, BFSK report code, BFSK relay that activates, and the text for the COMMAND 7 and COMMAND 9 keypad functions.

CMD7 Point Index

Default: 31

Selection: Blank (00) to 31

This entry selects one of the 31 P## Index codes that define how the control panel reacts when a COMMAND 7 is initiated.

The point index code used for COMMAND 7 must not be used for any other points on the system.

If the point index for COMMAND 7 has Fire points programmed as Yes, this causes access control doors to unlock if Fire Unlock is also programmed as Yes. Refer to the D9210B Program Entry Guide

(P/N: 32207).

Include the point number in custom point text. This helps the user when viewing events, creating bypasses, and so on. It can also simplify troubleshooting.

When a D1260 Keypad is installed on the system, the point text for Points 240 to 247 can be used for Area Name Text for Areas 1 to 8, respectively. Refer to Table

33:

Table 33: Point Text for Points 240 to 247

Point Text

Corresponding Area Name Text

Point 240

Area 1

Point 241

Area 2

Point 242

Area 3

Point 243

Area 4

Point 244

Area 5

Point 245

Area 6

Point 246

Area 7

Point 247

Area 8

 

 

CMD7 BFSK/Relay

Default: 1

Selection: 0 to 9

This entry selects one of the digits shown for reporting in BFSK or for activating relays 73 to 80 (on the D9412GV2) or relays 9 to 16 (for the D7412GV2) when COMMAND 7 is initiated (refer to the

P### BFSK/Relay prompt on page 103).

COMMAND 7 does not activate the

Summary Fire Alarm relay.

CMD7 Point Text

Default: [COMMAND][7]

Selection: Up to sixteen alphanumeric characters

Enter alphabetic characters A to Z in capital letters

Enter up to sixteen characters of text to describe the point. This point text appears at keypads (if the point is programmed as visible) and sent to the D6500 or D6600 when transmitting in Modem IIIa2 format (if it is a reporting point).