D# Auto Door?

D9412GV2/D7412GV2 Program Entry Guide 7.0 RADXAXS

EN 146

D# Auto Door?

Default:

No

Selection:

Yes or No

Yes

When the area assigned in D# Entry

 

Area # is disarmed, the door is in

 

the unlocked state. When that area

 

is armed, the door returns to the

 

locked state.

No

Door state is not affected by the

 

armed state of the area.

 

 

Use this program item to automatically unlock the door (latched, shunt, and strike) when the entry area is disarmed. The door re-locks upon Master or Perimeter Arming the area.

The unlocked state cannot be overridden manually.

D# Fire Unlock?

Default:

No

Selection:

Yes or No

Yes

Relay activates and shunt is applied

 

for the door contact automatically

 

upon a Fire Alarm.

 

 

No

Door remains in its current mode

 

upon a Fire Alarm.

Use this program item to activate the relay for the door strike and shunt the door zone automatically upon a Fire Alarm. This feature overrides a Secure Door state, Locked Door state, Auto Door, and an Interlock Faulted point. The relay activates for all doors with this prompt programmed as Yes when a Fire Alarm occurs in any area. Relays that are activated by Fire Unlock can be returned to normal only through the keypad using the Door Control function.

Doors that are activated by Fire Unlock must be returned to normal using the Door Control function on the keypad.

This command unlocks the door regardless of the armed state.

Each fire alarm that is generated causes a Door Unlocked – Automatic Event.

D# Disarm on Open?

Default:

Yes

Selection:

Yes or No

Yes

The area disarms only after the door

 

is opened for a user with a valid

 

disarm level.

 

 

No

The area disarms whether or not the

 

door is opened as soon as a user

 

with a valid disarm level presents a

 

valid token or card.

 

 

Use this program item to determine if the door needs to be physically opened before disarming the area upon a valid access request. The user initiating the access request needs access levels that allow disarming with ID.

D# Card Type

Default:

0

Selection:

0 to 3

0

Card format is 26-bit Wiegand.

 

 

3

Do not use. Card format is 37-bit

 

fidelity.

 

 

This item must be kept to a value of 0 (26 bit Wiegand format).