18-104
Cisco ONS 15600 SDH Procedure Guide, R8.0
October 2007
Chapter18 DLPs F300 to F399
DLP- F391 Install Alarm Wires on the CAP/CAP2
Step12 Return to your originating procedure (NTP).
DLP-F391 Install Alarm Wires on the CAP/CAP2
Step1 Wrap the alarm wires on the appropriate wire-wrap pins according to local site practice. Figure 18-27
shows the backplane of the ONS15600 SDH shelf and the location of the alarm pin field on the
CAP/CAP2.
Purpose This task installs the alarm wires on the customer access panel
(CAP/CAP2).
Tools/Equipment Wire-wrap tool (suitable for #22 to #28 AWG alarm wires)
#22 to #28 AWG wires
Audible alarm cable with DB-15 connector
Prerequisite Procedures NTP-F113 Install the Bay Power and Ground, page 1-10
Required/As Needed As needed
Onsite/Remote Onsite
Security Level None