Chapter 6: Applications 57
NOTE: For Avocent SPC power devices or Server Technology IPDUs, an alert window prompts you that the screen is automatically reloaded. Click OK and wait for confirmation that the page has been reloaded.
Applications - IPDU Power Mgmt. - Outlets Group Ctrl
An administrator can select Expert - Applications - IPDU Power Mgmt. - Outlet Groups Ctrl to view the status of outlet groups and turn power off and then on again for an entire group of outlets.
NOTE: Outlet groups can be defined under PMD Configuration - Outlet Groups.
The Cycle button only can be used to cycle the entire group of outlets when all the outlets are on.
The following table describes the information available from the Outlet Groups Ctrl form.
Table 6.3: Expert - Ouatlet Groups Ctrl Information
Form Heading
Group Name: Outlets
Group Ctrl
(IPDU and Port)
Description
IPDU Group name followed by the individual outlets belonging to that group.
Group Ctrl shows status icons for defined group controls; (IPDU and Port) shown in parentheses are the IPDU ID number and the serial port to which it is connected on the console server. Status icons under the Group Ctrl heading are active.
Individual Status | Shows status icons (passive) for individual outlets within the group. |
Applications - IPDU Power Mgmt. - View IPDUs Info
An administrator can select Expert - Applications - IPDU Power Mgmt. - View IPDUs Info to view information about each IPDU controlled by the console server.
The buttons to Clear/Reset Max values will be displayed when the IPDU has the max detected value for the sensor. Possible buttons:
•Clear Max Current - reset the maximum detected current value
•Clear Max Power - reset the maximum detected or estimated power consumption value
•Reset Max Env Sensors - reset the maximum detected value of environmental sensors (Temperature, Humidity, Air Flow)
•Reset HW OCP - reset the HW over current protection (valid only for Avocent PM PDUs)
•Reset Max Voltage - reset the maximum detected voltage value
•Reset Max Power Factor - reset the maximum detected power factor