If the detection band value + the set frequency is less than the designated frequency

Output frequency [Hz]

H + H H

H - H

0

Time [s]

 

Set frquency speed reach signal RY-RC terminals FLA-FLC-FLB terminals

Set frequency speed reach signal: Inverted

ON OFF

ON OFF

6.2Input signal selection

6.2.1Changing the functions of VIA terminal

6

H : VIA terminal function selection

Function

This parameter allows you to choose between signal input and contact signal input for the VIA terminal.

[Parameter setting]

Title

Function

Adjustment range

Default setting

 

 

0: VIA - analog input

 

 

Analog/contact input

1: VIA - contact input (Sink)

0

H

function selection

 

 

(VIA terminal)

2: VIA - contact input (Source)

 

 

 

 

 

 

 

 

*When using the VIA terminal as contact input terminals in sink logic connection, be sure to insert a resistor between the P24 terminal and the VIA terminal. (Recommended resistance: 4.7k-1/2W)

Note: When using the VIA terminal as a contact input terminal, be sure to turn the VIA (SW3) slide switch to the V position.

+The figure on the right shows an example of the connection of input terminal VIA when it is used as contact input terminal. This example illustrates the connection when the inverter is used in sink (Negative) logic mode.

F-4

Page 100
Image 100