E6581381
5.10 Selecting control mode
RV : V/F control mode selection
•Function
With
{V/F constant
{Variable torque
{Automatic torque boost control
{Vector control
{Energy saving
{PM motor control
[Parameter setting]
|
| Title | Function | Adjustment range | Default setting |
5 |
|
|
| 0: V/F constant |
|
|
|
|
| 1: Variable torque |
|
|
|
| V/F control mode selection | 2: Automatic torque boost control |
|
|
|
|
| ||
|
| RV | 3: Vector control | 1 | |
|
|
|
| 4: |
|
|
|
|
| 5: - (Do not select) |
|
|
|
|
| 6: PM motor control |
|
|
| Steps in setting are as follows |
|
|
(In this example, the V/F control mode selection parameter RV is set to (Vector control).
■Setting V/F control mode selection to 3 (sensorless vector control)
Key operated | LED display | Operation | |||||
|
| Displays the operation frequency. (Perform during operation stopped.) | |||||
| . | (When standard monitor display selection H is set to | |||||
|
| [Operation frequency]) | |||||
MODE | CWH | The first basic parameter “CWH” (Wizard function) is displayed. | |||||
|
|
|
|
|
|
| |
| RV | Press the |
|
| key to change the parameter to RV (V/F control mode | ||
|
|
| |||||
| selection). | ||||||
|
| ||||||
ENT | Press the ENT key to display the parameter setting. (Standard | ||||||
default setting: ( Variable torque)). | |||||||
|
| ||||||
| Press the |
| key to change the parameter to (vector control). | ||||
|
| ||||||
|
| ||||||
|
|
|
|
|
|
| |
ENT | ⇔ RV | Press the ENT key to save the changed parameter. RV and | |||||
parameter set value “” are displayed alternately. | |||||||
|
|