Toshiba VF-FS1 Output of designated frequency reach signal,  Speed reach detection band

Models: VF-FS1

1 252
Download 252 pages 5.48 Kb
Page 98
Image 98

E6581381

An example of the connection of the relay output terminals

Output terminal setting

Output of the low-speed signal (ON signal) between the RY and RC terminals is the factory default setting of the output terminal selection parameter. This setting must be changed to invert the polarity of the signal.

[Parameter setting]

 

 

Title

Function

Adjustment range

Setting value

 

 

H

Output terminal selection 1A (RY-RC)

0-255

4 (ON signal)

 

 

or

 

 

(See page K-17)

 

 

 

 

5 (OFF signal)

6

 

 

 

 

 

 

 

 

 

6.1.2Output of designated frequency reach signal

H : Speed reach detection band

Function

When the output frequency becomes equal to the setting by designated frequency ±H, an ON or OFF signal is generated.

[Parameter setting]

Title

 

Function

 

Adjustment range

 

Default setting

H

Speed reach detection band

0.0 HJ (Hz)

 

2.5

[Parameter setting]

 

 

 

 

 

 

Title

Function

 

Adjustment range

Setting value

 

H

Output terminal

0-255

 

6: RCH (designated frequency - ON signal), or

selection 1A

 

 

 

(See page K-17)

 

7: RCHN (designated frequency - OFF signal)

 

(RY-RC)

 

 

 

 

 

 

 

 

 

Note: Select the H parameter to specify FLA-FLC-FLB terminal output.

F-2

Page 98
Image 98
Toshiba VF-FS1 instruction manual Output of designated frequency reach signal,  Speed reach detection band