6.17.12 Undervoltage trip

H : Undervoltage trip/alarm selection

Function

This parameter is used for selecting the control mode when an undervoltage is detected. Trip information is displayed as "WR".

H=: The inverter is stopped. However, it is not tripped (Failure signal FL not activated). The inverter is stopped when the voltage does not exceed 60 % or less of its rating.

H=: Inverter is stopped. It is also tripped (Failure signal FL activated), only after detection of a voltage not exceeding 60% or less of its rating.

H=: Inverter is stopped. However, it is not tripped (Failure signal FL not activated). The inverter stop (Failure signal FL not activated.), only after detection of a voltage not exceeding 50% of its rating. Be sure to connect the input reactor.

 

 

Title

Function

Adjustment range

Default setting

 

 

 

Undervoltage trip/alarm

0: Alarm only (detection level below 60%)

 

6

 

H

1: Tripping (detection level below 60%)

0

 

 

selection

2: Alarm only (detection level below 50%,

 

 

 

 

input reactor needed)

 

 

 

 

 

 

 

F-64

Page 160
Image 160
Toshiba VF-FS1 instruction manual  Undervoltage trip/alarm selection