E6581381
3.1.1How to start and stop
■Example of a EOQF setting procedure
Key operated | LED display |
|
|
|
| Operation | |||
|
| Displays the operation frequency (operation stopped). | |||||||
| (When standard monitor display selection H=[Operation | ||||||||
|
| frequency]) | |||||||
MODE | CWH | Displays the first basic parameter [Wizard function (CWH)]. | |||||||
|
|
|
|
|
|
|
|
| |
| EOQF | Press either the |
| or |
| key to select “EOQF”. | |||
|
| ||||||||
|
|
| |||||||
|
|
|
|
|
|
|
|
| |
ENT | Press ENT key to display the parameter setting. (Default setting:). | ||||||||
|
|
|
|
|
|
|
|
| |
| Change the parameter to (panel) by pressing the |
| key. | ||||||
|
| ||||||||
|
| ||||||||
|
|
|
|
|
|
|
|
| |
ENT | ⇔EOQF | Press the ENT key to save the changed parameter. EOQF and the | |||||||
parameter set value are displayed alternately. | |||||||||
|
|
(1) Start and stop using the operation panel keys (EOQF=)
Use the RUN and STOP keys on the operation panel to start and stop the motor.
RUN : Motor starts. | STOP : Motor stops. |
+To switch between forward run and reverse run from the control panel, the parameter HT (forward/reverse run selection) needs to be set to or .
(2)RUN/STOP by means of an external signal to the terminal board (EOQF=): Sink (Negative) logic
Use external signals to the inverter terminal board to start and stop the motor.
Short | F | and | CC | terminals: run forward |
| Slow down | |
Frequency | and stop | ||||||
|
|
|
|
| |||
Open |
| and |
| terminals: slow down and stop |
| ON | |
F | CC | ||||||
OFF | |||||||
|
|
|
|
|
|
|
3
(3) Coast stop
The standard default setting is for slowdown stop. To make a coast stop, assign a "1(ST)" terminal function to an idle terminal using the programmable terminal function.
Change to H=.
For coast stop, open the
inverter at this time will display QHH.
Motor speed
Coast stop
ON
OFF
ON
OFF