<<Sample sequence diagram 2: Adjustment with pulse signals>>
|
| ■ If two signals are impressed simultaneously |
6 |
| |
| • If a clear single and an up or down signal are impressed simultaneously, priority will be given to the | |
|
| |
|
| clear signal. |
|
| |
|
| • If up and down signals are impressed simultaneously, The frequency will change at the specified up |
|
| or down rate. |
|
| ■ About the setting of the initial up/down frequency |
|
| To adjust the frequency starting at a specified frequency other than 0.0 Hz (default initial frequency) |
|
| after turning on the inverter, specify the desired frequency using H (initial up/down frequency). |
|
| ■ About the change of the initial up/down frequency |
|
| To make the inverter automatically save the frequency immediately before it is turned off and start |
|
| operation at that frequency next time power is turned on, set H (change of initial up/down |
|
| frequency) to 1 (which changes the setting of H when power is turned off). |
|
| Keep in mind that the setting of H is changed each time power is turned off. |
|
| ■ Frequency adjustment range |
|
| The frequency can be set from 0.0Hz to HJ (Maximum frequency). The |
|
| set as soon as the set frequency clearing function (function number 43, 44) is entered from the input |
|
| terminal. |
|
| ■ Minimum unit of frequency adjustment |
|
| If H (Frequency free unit magnification) is set to 1.00, the output frequency can be adjusted in |
|
| steps of 0.01Hz. |
|
|
|
|
|