<<Sample sequence diagram 2: Adjustment with pulse signals>>

 

 

■ If two signals are impressed simultaneously

6

 

 

If a clear single and an up or down signal are impressed simultaneously, priority will be given to the

 

 

 

 

clear signal.

 

 

 

 

If up and down signals are impressed simultaneously, The frequency will change at the specified up

 

 

or down rate.

 

 

■ About the setting of the initial up/down frequency

 

 

To adjust the frequency starting at a specified frequency other than 0.0 Hz (default initial frequency)

 

 

after turning on the inverter, specify the desired frequency using H (initial up/down frequency).

 

 

■ About the change of the initial up/down frequency

 

 

To make the inverter automatically save the frequency immediately before it is turned off and start

 

 

operation at that frequency next time power is turned on, set H (change of initial up/down

 

 

frequency) to 1 (which changes the setting of H when power is turned off).

 

 

Keep in mind that the setting of H is changed each time power is turned off.

 

 

■ Frequency adjustment range

 

 

The frequency can be set from 0.0Hz to HJ (Maximum frequency). The lower-limit frequency will be

 

 

set as soon as the set frequency clearing function (function number 43, 44) is entered from the input

 

 

terminal.

 

 

■ Minimum unit of frequency adjustment

 

 

If H (Frequency free unit magnification) is set to 1.00, the output frequency can be adjusted in

 

 

steps of 0.01Hz.

 

 

 

 

 