E6581381

5.6Forward/reverse run selection (Operation panel operation)

HT : Forward/reverse run selection (Operation panel operation)

Function

Program the direction of rotation of the motor when the running and stopping are made using the RUN key and STOP key on the operation panel.

Valid when EOQF (command mode) is set to  (operation panel).

[Parameter setting]

Title

Function

Adjustment range

Default setting

 

 

 

0: Forward run

 

 

 

 

 

1: Reverse run

 

 

5

HT

Forward/reverse run selection

2: Forward run (F/R switching

0

 

(Operation panel operation)

possible)

 

 

 

 

 

 

 

 

3: Reverse run (F/R switching

 

 

 

 

 

possible)

 

 

 

+When HT is set to  or  and an operating status is displayed, pressing the key with the ENT key held down changes the direction of rotation from reverse to forward after displaying the message

“HTH” Pressing the key again with the ENT key held down changes the direction of rotation from forward to reverse after displaying the message “HTT”

+Check the direction of rotation on the status monitor. For monitoring, see section 8.1

HTH: Forward run

HTT: Reverse run

+When the F and R terminals are used for switching between forward and reverse rotation from the terminal board, the HT forward/reverse run selection parameter is rendered invalid.

Short across the F-CC terminals: forward rotation

Short across the R-CC terminals: reverse rotation.

+The inverter was factory-configured by default so that shorting terminals F-CC and terminals R-CC simultaneously would cause the motor to slow down to a stop.

Using the parameter H, however, you can select between forward run and reverse run.

+This function is valid only when EOQF is set to  (operation panel).

E-15

Page 81
Image 81
Toshiba VF-FS1 instruction manual Forward/reverse run selection Operation panel operation