E6581381

 

 

 

 

 

 

 

 

 

 

 

 

Title

 

 

Function

Adjustment range

 

 

Default setting

 

H

Small current detection current hysteresis

1-20 (%)

 

 

10

 

 

H

Small current trip/alarm selection

0: Alarm only

 

 

0

 

 

1: Tripping

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

Small current detection current

0-100 (%) / (A)

 

 

0

 

 

H

Small current detection time

0-255 [s]

 

 

0

 

 

Example of operation

 

 

 

 

 

 

 

Output terminal function: 24 (UC) Low current detection

 

 

 

 

 

 

H =  (Alarm only)

 

 

ON

 

 

 

 

 

 

 

Low current

 

 

OFF

 

 

OFF

 

signal output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output current (%)

H or less

H

6

H+H

 

 

H

 

 

 

 

 

Time [sec]

*When setting H to  (Trip), trip after low current detection time setting of H. After tripping, the low current signal remains ON.

6.17.8 Detection of output short-circuit

H : Detection of output short-circuit during start-up

Function

This parameter detects inverter output short-circuit. It can be usually detected in the length of the standard pulse. When operating low-impedance motor such as high-speed motor, however, the short- time pulse should be selected.

H=: Detection is executed in the length of the standard pulse every time you start up the inverter.

H=: Detection is executed in the length of standard pulse only during the first start-up after putting on the power or after resetting.

H=: Detection is executed with the short-time pulse every time you start up the inverter.

H=: Detection is executed with the short-time pulse only for the first time after putting power on or after resetting.

F-60